Nortec LINKS XPS MH User Manual
Page 50
47 | Links XPS for MHTC
Table 11: Humidifier Variable Addresses - Unit #5
Unit #5
BACnet
Lonworks
N2
Variable Name
Type Instance
SNVT
SNVT # Element
Type
Instance
nvoServTime_5 AV
45
SNVT_lev_count_f 55
101 Ana_Output
45
nvoPumpRunHr_5 AV
46
SNVT_lev_count_f 55
102 Ana_Output
46
nvoUVRunHr_5 AV
47
SNVT_lev_count_f 55
103 Ana_Output
47
nvoSet1_5
AV
48
SNVT_lev_count_f 55
104 Ana_Output
48
nvoHum_Control_5 AV
49
SNVT_lev_count_f 55
105 Ana_Output
49
nvoCapLimit_5 AV
50
SNVT_lev_count_f 55
106 Ana_Output
50
nvoRHDem1_5 AV
51
SNVT_lev_count_f 55
107 Ana_Output
51
nviSet1_5
AV
52
SNVT_lev_count_f 55
108 Ana_Output
52
nviRHDem1_5 AV
53
SNVT_lev_count_f 55
109 Ana_Output
53
nviHum_Control_5 AV
54
SNVT_lev_count_f 55
110 Ana_Output
54
nviCapLimit_5
AV
55
SNVT_lev_count_f 55
111 Ana_Output
55
nvoNetSensor_5 BV
57
SNVT_switch
95
112
Dig_Output
57
nvoDisable_5
BV
58
SNVT_switch
95
113
Dig_Output
58
nvoStage1Dem_5 BV
59
SNVT_switch
95
114
Dig_Output
59
nvoStage2Dem_5 BV
60
SNVT_switch
95
115
Dig_Output
60
nvoStage3Dem_5 BV
61
SNVT_switch
95
116
Dig_Output
61
nvoWarning_5
BV
62
SNVT_switch
95
117
Dig_Output
62
nvoService_5
BV
63
SNVT_switch
95
118
Dig_Output
63
nvoFault_5
BV
64
SNVT_switch
95
119
Dig_Output
64
nvoCleaning_5
BV
65
SNVT_switch
95
120
Dig_Output
65
nvoTankDrain_5 BV
66
SNVT_switch
95
121
Dig_Output
66
nvoSecurity_5
BV
67
SNVT_switch
95
122
Dig_Output
67
nvoTankLevel_5 BV
68
SNVT_switch
95
123
Dig_Output
68
nviNetSensor_5 BV
69
SNVT_switch
95
124
Dig_Output
69
nviDisable_5
BV
70
SNVT_switch
95
125
Dig_Output
70