Nortec LINKS XPS MH User Manual
Page 49
Links XPS for MHTC | 46
Table 10: Humidifier Variable Addresses - Unit #4
Unit #4
BACnet
Lonworks
N2
Variable Name
Type Instance
SNVT
SNVT # Element
Type
Instance
nvoServTime_4 AV
34
SNVT_lev_count_f 55
76
Ana_Output
34
nvoPumpRunHr_4 AV
35
SNVT_lev_count_f 55
77
Ana_Output
35
nvoUVRunHr_4 AV
36
SNVT_lev_count_f 55
78
Ana_Output
36
nvoSet1_4
AV
37
SNVT_lev_count_f 55
79
Ana_Output
37
nvoHum_Control_4 AV
38
SNVT_lev_count_f 55
80
Ana_Output
38
nvoCapLimit_4 AV
39
SNVT_lev_count_f 55
81
Ana_Output
39
nvoRHDem1_4 AV
40
SNVT_lev_count_f 55
82
Ana_Output
40
nviSet1_4
AV
41
SNVT_lev_count_f 55
83
Ana_Output
41
nviRHDem1_4 AV
42
SNVT_lev_count_f 55
84
Ana_Output
42
nviHum_Control_4 AV
43
SNVT_lev_count_f 55
85
Ana_Output
43
nviCapLimit_4
AV
44
SNVT_lev_count_f 55
86
Ana_Output
44
nvoNetSensor_4 BV
43
SNVT_switch
95
87
Dig_Output
43
nvoDisable_4
BV
44
SNVT_switch
95
88
Dig_Output
44
nvoStage1Dem_4 BV
45
SNVT_switch
95
89
Dig_Output
45
nvoStage2Dem_4 BV
46
SNVT_switch
95
90
Dig_Output
46
nvoStage3Dem_4 BV
47
SNVT_switch
95
91
Dig_Output
47
nvoWarning_4
BV
48
SNVT_switch
95
92
Dig_Output
48
nvoService_4
BV
49
SNVT_switch
95
93
Dig_Output
49
nvoFault_4
BV
50
SNVT_switch
95
94
Dig_Output
50
nvoCleaning_4
BV
51
SNVT_switch
95
95
Dig_Output
51
nvoTankDrain_4 BV
52
SNVT_switch
95
96
Dig_Output
52
nvoSecurity_4
BV
53
SNVT_switch
95
97
Dig_Output
53
nvoTankLevel_4 BV
54
SNVT_switch
95
98
Dig_Output
54
nviNetSensor_4 BV
55
SNVT_switch
95
99
Dig_Output
55
nviDisable_4
BV
56
SNVT_switch
95
100
Dig_Output
56