Links XPS for MHTC | 18

Wiring

BACnet MS/TP, Johnson N2, and LonWorks

Links XPS is pre-installed and factory wired. Connections must be made between the master
humidifier and the BMS, and the master humidifier and any slaves that may be present.

Up to 8 units (1 master, 7 slaves) may be connected to a BMS through a single gateway in the
master unit. The units are daisy chained via the Links XPS terminal strip. The wire shield
should only be connected at one end per pair of units when “daisy chaining”.

Table 2 refers to the recommended wire types and maximum recommended lengths from the
Nortec Links XPS module to the Building Management system. Communication between the
humidifiers and Nortec Links XPS will occur via a EIA-485 signal type. Nortec recommends using
a 18-24 AWG shielded, 120

twisted pair wire between the lead humidifier and each of the

slave humidifiers. Total cable length runs between the Nortec Links XPS module and the
furthest slave humidifier should not exceed 2,000 feet. Signal boosters or repeaters may be
necessary for longer wire runs or where electrical noise interference is prevalent.

Table 2: Recommended Wire Types and Lengths

Protocol

Signal

Type

Polarity

Recommended

Cable

Maximum

Recommended Distance

from Nortec Module

A

B

BACnet MS/TP

EIA-485,

2-wire

Net +

Net -

18-24 AWG

Shielded, Twisted

Pair

120

Impedance

2300 ft at 9.6 kbps

2000 ft at 38.4 kbps

Johnson N2

LonWorks

FTT-10, 2-

wire

Tx

Rx

18-24 AWG

Twisted Pair

120

Impedance

Should not exceed 50 ft.

BACnet/IP

LAN

standard

N/A

N/A

CAT.5E cable with
RJ-45 termination

Depends on cable

manufacturer