Nortec LINKS XPS MH User Manual
Page 47
Links XPS for MHTC | 44
Table 8: Humidifier Variable Addresses - Unit #2
Unit #2
BACnet
Lonworks
N2
Variable Name
Type Instance
SNVT
SNVT # NV Index
Type
Instance
nvoServTime_2 AV
12
SNVT_lev_count_f 55
26
Ana_Output
12
nvoPumpRunHr_2 AV
13
SNVT_lev_count_f 55
27
Ana_Output
13
nvoUVRunHr_2 AV
14
SNVT_lev_count_f 55
28
Ana_Output
14
nvoSet1_2
AV
15
SNVT_lev_count_f 55
29
Ana_Output
15
nvoHum_Control_2 AV
16
SNVT_lev_count_f 55
30
Ana_Output
16
nvoCapLimit_2 AV
17
SNVT_lev_count_f 55
31
Ana_Output
17
nvoRHDem1_2 AV
18
SNVT_lev_count_f 55
32
Ana_Output
18
nviSet1_2
AV
19
SNVT_lev_count_f 55
33
Ana_Output
19
nviRHDem1_2 AV
20
SNVT_lev_count_f 55
34
Ana_Output
20
nviHum_Control_2 AV
21
SNVT_lev_count_f 55
35
Ana_Output
21
nviCapLimit_2
AV
22
SNVT_lev_count_f 55
36
Ana_Output
22
nvoNetSensor_2
BV
15
SNVT_switch
95
37
Dig_Output
15
nvoDisable_2
BV
16
SNVT_switch
95
38
Dig_Output
16
nvoStage1Dem_2 BV
17
SNVT_switch
95
39
Dig_Output
17
nvoStage2Dem_2 BV
18
SNVT_switch
95
40
Dig_Output
18
nvoStage3Dem_2 BV
19
SNVT_switch
95
41
Dig_Output
19
nvoWarning_2
BV
20
SNVT_switch
95
42
Dig_Output
20
nvoService_2
BV
21
SNVT_switch
95
43
Dig_Output
21
nvoFault_2
BV
22
SNVT_switch
95
44
Dig_Output
22
nvoCleaning_2
BV
23
SNVT_switch
95
45
Dig_Output
23
nvoTankDrain_2
BV
24
SNVT_switch
95
46
Dig_Output
24
nvoSecurity_2
BV
25
SNVT_switch
95
47
Dig_Output
25
nvoTankLevel_2
BV
26
SNVT_switch
95
48
Dig_Output
26
nviNetSensor_2
BV
27
SNVT_switch
95
49
Dig_Output
27
nviDisable_2
BV
28
SNVT_switch
95
50
Dig_Output
28