Table 6: Variable Definitions - CONTINUED

Variable Name

R=Read

W=Write

Description

nvoHum_Control_x

R

Analog Value

Read control mode status.
0 = Demand Signal
1 = On/Off signal
2 = Sensed RH signal, humidifier used proportional algorithm
3 = Sensed RH signal, humidifier uses proportional-integral
algorithm

nvoServTime_x

R

Analog Value

Indicates operation hours.

nvoPumpRunHr_x

R

Analog Value

Indicates total run hours of pump since manufacture.

nvoUVRunHr_x

R

Analog Value

Indicates total run hours of UV since last reset.

nvoStage1Dem_x

R

Binary Value

Indicates if stage 1 is actively humidifying.
1 = On
2 = Off

nvoStage2Dem_x

R

Binary Value

Indicates if stage 2 is actively humidifying.
1 = On
2 = Off

nvoStage3Dem_x

R

Binary Value

Indicates if stage 3 is actively humidifying.
1 = On
2 = Off

nvoWarning_x

R

Binary Value

Indicates that a warning is present on the humidifier. Check
humidifier display for warning information.
1 = Warning
0 = No Warning

nvoCleaning_x

R

Binary Value

Indicates that a cleaning cycle is active.
1 = Clean Cycle Active
0 = Inactive

nvoTankDrain_x

R

Binary Value

Indicates that tank drain is active.
1 = Drain Cycle Active
0 = Inactive

nvoTankLevel_x

R

Binary Value

Indicates Tank Water Level.
1 = Full Water
0 = Below Full