Nortec LINKS XPS MH User Manual
Page 45
Links XPS for MHTC | 42
Table 6: Variable Definitions - CONTINUED
Variable Name
R=Read
W=Write
Description
nvoHum_Control_x
R
Analog Value
Read control mode status.
0 = Demand Signal
1 = On/Off signal
2 = Sensed RH signal, humidifier used proportional algorithm
3 = Sensed RH signal, humidifier uses proportional-integral
algorithm
nvoServTime_x
R
Analog Value
Indicates operation hours.
nvoPumpRunHr_x
R
Analog Value
Indicates total run hours of pump since manufacture.
nvoUVRunHr_x
R
Analog Value
Indicates total run hours of UV since last reset.
nvoStage1Dem_x
R
Binary Value
Indicates if stage 1 is actively humidifying.
1 = On
2 = Off
nvoStage2Dem_x
R
Binary Value
Indicates if stage 2 is actively humidifying.
1 = On
2 = Off
nvoStage3Dem_x
R
Binary Value
Indicates if stage 3 is actively humidifying.
1 = On
2 = Off
nvoWarning_x
R
Binary Value
Indicates that a warning is present on the humidifier. Check
humidifier display for warning information.
1 = Warning
0 = No Warning
nvoCleaning_x
R
Binary Value
Indicates that a cleaning cycle is active.
1 = Clean Cycle Active
0 = Inactive
nvoTankDrain_x
R
Binary Value
Indicates that tank drain is active.
1 = Drain Cycle Active
0 = Inactive
nvoTankLevel_x
R
Binary Value
Indicates Tank Water Level.
1 = Full Water
0 = Below Full