23 | Links XPS for MHTC

After an address change has been made, the Links XPS module must be power cycled for the
change to take effect. The module may take up to 60 seconds to restart after a power cycle.

Changing Baud Rate (BACnet MSTP, Johnson N2, LonWorks)

The baud rate for communications must be changed through dipswitches (SW4 Bank, 1 through
4). Refer to figure 16 for location of the dipswitch.

By adjusting the settings according to the table 5, the baud rate can be changed. The Baud rate
must be set to exactly the same baud rate as your Building Management System.
Communication performance varies with building automation system manufacturer and some
experimentation with other baud rates may be required to obtain the best performance.

Table 5: Common Settings

Setting

B4

B3

B2

B1

110

Off

Off

Off

On

300

Off

Off

On

Off

600

Off

Off

On

On

1200

Off

On

Off

Off

2400

Off

On

Off

On

4800

Off

On

On

Off

9600

Off

On

On

On

19200

On

Off

Off

Off

20833

On

Off

Off

On

28800

On

Off

On

Off

38400

On

Off

On

On

57600

On

On

Off

Off

76800

On

On

Off

On

115200

On

On

On

Off

After an address change has been made, the Links XPS module must be power cycled for the
change to take effect. The module may take up to 60 seconds to restart after a power cycle.