Nortec LINKS XPS MH User Manual
Page 26
23 | Links XPS for MHTC
After an address change has been made, the Links XPS module must be power cycled for the
change to take effect. The module may take up to 60 seconds to restart after a power cycle.
Changing Baud Rate (BACnet MSTP, Johnson N2, LonWorks)
The baud rate for communications must be changed through dipswitches (SW4 Bank, 1 through
4). Refer to figure 16 for location of the dipswitch.
By adjusting the settings according to the table 5, the baud rate can be changed. The Baud rate
must be set to exactly the same baud rate as your Building Management System.
Communication performance varies with building automation system manufacturer and some
experimentation with other baud rates may be required to obtain the best performance.
Table 5: Common Settings
Setting
B4
B3
B2
B1
110
Off
Off
Off
On
300
Off
Off
On
Off
600
Off
Off
On
On
1200
Off
On
Off
Off
2400
Off
On
Off
On
4800
Off
On
On
Off
9600
Off
On
On
On
19200
On
Off
Off
Off
20833
On
Off
Off
On
28800
On
Off
On
Off
38400
On
Off
On
On
57600
On
On
Off
Off
76800
On
On
Off
On
115200
On
On
On
Off
After an address change has been made, the Links XPS module must be power cycled for the
change to take effect. The module may take up to 60 seconds to restart after a power cycle.