Introduction

CB-7000 is a family of network data acquisition and control modules. They provide A/D, D/A, DI/O,
Timing/Counting and other functions. These modules can be remote controlled by a set of commands.

The common features of CB-7080 and CB-7080D include:

 Two independent 32-bit counters, counter 0 and counter 1.

 Input signals can be isolated or non-isolated.

 Programmable digital filter for isolated and non-isolated input.

 External gate control for isolated and non-isolated input.

 Programmable threshold value for non-isolated input.

 Programmable alarm output.

 Input frequency measurement up to 100 kHz.

The CB-7080D module identical to the CB-7080 with a 5-digit LED display added. The LEDs can display the
counter value and input signal frequency without PC control.

Comparing the 7080 and 7080D

Table 1-1 summarizes the features of the CB7080 and CB7080D modules.

Table 1-1. Comparison between CB-7080 and CB-7080D

CB-7080

CB-7080D

5-digit LED display

No

Yes

Response to LED command

No

Yes

Module name

programmable

programmable

Counter preset value

Yes (programmable)

Yes (programmable)

Alarm on counter 0 only

Yes (programmable)

Yes (programmable)

Alarm on counter 0 and 1

Yes (programmable)

Yes (programmable)

Channel 0 and channel 1 are both non-
isolated (input mode 0, $AAB0)

Yes

Yes

Channel 0 and channel 1 are both
isolated (input mode 1, $AAB1)

Yes

Yes

Channel 0 is non-isolated and channel
1 is isolated (input mode 2, $AAB2)

Yes

Yes

Channel 0 is isolated and channel 1 is
non-isolated(input mode 3, $AAB3)

Yes

Yes

Input frequency

100 kHz max.

100 kHz max.

Default setting

4080 compatible

High alarm on counter 0
and 1

Counter preset value: 0

4080D compatible

High/High-High alarm on counter 0

Counter preset value: 0

This manual is related to the following products: