Troubleshooting, Electric heater does not operate (optional) – Greenheck MSX (470658) User Manual

Page 31

background image

31

Modular Supply Make-Up Air Unit

®

Troubleshooting

Electric Heater Does Not Operate (optional)

Supply fan must be on for heater to operate

24 VAC between

terminals W1 and X?

24 VAC between

terminals 22 and 21?

24 VAC between

terminals I and 21?

24 VAC between

terminals T1 and 21?

24 VAC between

terminal A2 on heat relay (RH)

and X?

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Heat Switch (S4) Off

(Turn Heat Switch (S4) On)

Heat Switch not wired

(Wire Heat Switch (S4))

Main Transformer (TR2) defective

(Replace transformer)

Heat Relay (RH) is not energized

(Check for loose connections). (Repair or replace Heat Relay (RH))

(Optional) Inlet Air Sensor (TS4) holding

(Adjust (TS4) setting. Reference Blower Start-Up Step #6)

At this time the heater should be energized.

(The heating elements will not be on if the leaving air

temperature is above its set point on the Remote Adjuster (RA))

Pressure Differential Switch (PDS) open

(Check on cause of control loss)

Automatic and/or Manual Reset Cutouts (A and M) tripped

(Reset/Replace Automatic and/or Manual Reset Cutouts (A and M))

(Check on cause of control loss)