beautypg.com

Troubleshooting, Blower does not operate – Greenheck MSX (470658) User Manual

Page 27

background image

27

Modular Supply Make-Up Air Unit

®

Proper supply power at

main disconnect

24 VAC between

terminals R and X?

24 VAC between

terminals G and X?

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Blower Does Not Operate

24 VAC across A2 and A1 on

supply contactor (ST1)

24 VAC across

terminals 4 and X?

24 VAC across

terminals 3 and X?

Troubleshooting

Check main voltage

(See Blower Start-Up Step #1)

Main Disconnect (DS1) Off

(Turn Main Disconnect DS1 On)

Primary fuses blown

(Replace fuses)

Main Transformer (TR1) Defective

(Replace transformer)

Supply Switch (S2) Off

(Turn Supply Switch (S2) On)

Fire System Contact (FSC) tripped/not installed

(Correct/Replace)

Broken fan belt

(Replace. Reference Maintenance section)

Defective motor or capacitor

(Repair/Replace)

Blown motor fuse

(Replace)

One or more legs of 3 phase is out

(Restore missing legs)

Supply Fan Overload (ST1 OL) tripped

(Reset and check motor amps. Reference Blower Start-Up #4)

Optional Exhaust Fan Interlocks (ST2-ST5) open

(Correct/Replace)

(Optional) Damper Limit Switch (DL1) holding

(Wait for actuator to open fully or adjust limit switch)

(Optional) Damper Limit Switch jumper missing

(Install jumper. Reference the unit’s ladder diagram for terminals)

Fan Relay (RF) is not energized

(Check for loose connection) (Repair or replace relay)

(Optional) Freeze Protection (RT4) Tripped

(Reset)

At this time the supply contactor (ST1) should pull in,

passing power to the supply motor

and the blower should start.