beautypg.com

Auto drain & fill evaporative piping – Greenheck MSX (470658) User Manual

Page 10

background image

10

Modular Supply Make-Up Air Unit

®

Installation Evaporative Cooler Piping
(optional)
Recirculating Evaporative Piping

IMPORTANT

All supply solenoids, valves and all traps must be below
the roof line or be otherwise protected from freezing.

IMPORTANT

The supply line should be of adequate size and
pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be
the same size or larger than the supply line.

CAUTION

Provisions must be taken to prevent damage to the
evaporative cooling section during freezing conditions.
The sump, drain lines and supply lines must be drained
prior to freezing conditions or an alternate method must
be used to protect the lines and media.

Evaporative Cooling with Recirculating Pump

1. Install the Water Supply Line. Supply line opening

requirements vary by unit size and arrangement and
are field supplied. Connect the water supply line to
the float valve through the supply line opening in
the evaporative cooling unit. Install a manual shutoff
valve in the supply line as shown.

2. Install the Drain Line. Connect an unobstructed

drain line to the drain and overflow connections on
the evaporative cooler. A manual shut off valve (by
others) is required for the evaporative cooler drain
line.

A trap should be used to prevent sewer gas from
being drawn into
the unit.

3. Check/Adjust

Water Level.
Check the water
level in the sump
tank. The water
level should be
above the pump
intake and below the overflow. Adjust the float as
needed to achieve the proper water level.

Supply

Line

Overflow

Trap

Drain Line Valve

(By Others)

Drain Line

Supply Line

Valve

(By Others)

6 in. min.

6 in. min.

Drain Trap

Auto Drain & Flush Valves

(When provided by Manufacturer)

Assembly

Number

Mfg

Part

Number

ASCO

Part

Number

Solenoid

Type

De-Energized

Position

Diameter Qty.

852178

461262 8210G2

Supply

Closed

1/2 inch

(12.7 mm)

1

461263 8262G262

Supply

Line

Drain

Open

1/4 inch

(6.35 mm)

1

461264 8210G35

Sump

Drain

Open

3/4 inch

(19.05 mm)

1

Part numbers subject to change.

IMPORTANT

The supply line should be of adequate size and
pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be
the same size or larger than the supply line.

CAUTION

All solenoids valves and traps must be installed below the
roof to protect the supply water line from freezing. If they
cannot be installed below the roof, an alternative method
must be used to protect the lines from freezing.

IMPORTANT

The supply solenoid (Valve A) is NOT the same as the
drain solenoids (Valve B and Valve C). Make sure to
use the proper solenoid for each location. Check your
local code requirements for proper installation of this
type of system.

Auto Drain & Fill Evaporative Piping

1. Install the Water Supply Line. Supply line opening

requirements vary by unit size and arrangement and
are field supplied. Connect the water supply line to
the float valve through the supply line opening in the
evaporative cooling unit. Install the 1/2 in. normally
closed solenoid (Valve A) in the supply line. Install the
1/4 in. normally open solenoid (Valve B) between the
supply line and the drain line. Refer to Auto Drain &
Fill Evaporative Piping drawing on previous page.

2. Install the Drain Line. Connect an unobstructed

drain line to the sump drain overflow connection.
Install the 3/4 in. normally open solenoid (Valve C)
between the
sump drain
connection and
the drain line. A
trap should be
used to prevent
sewer gas from
being drawn into the unit.

3. Check/Adjust Water Level. Check the water level

in the sump tank. The water level should be above
the pump intake and below the overflow. Adjust the
float as needed to achieve the proper water level.

6 in. min.

6 in. min.

Drain Trap