Start-up - water wizard™ (optional) – Greenheck MSX (470658) User Manual

Page 21

background image

21

Modular Supply Make-Up Air Unit

®

Water Wizard™ User Interface

Key Function Description

Recommended Water Pressure Chart

Housing

Size

Media Width

(inches)

Water Pressure

(in. wc)

MSX-H12

30

20

MSX-H22

43

3

4

36

60

61

MSX-H32

66

72

96*

42

MSX-H35

120*

61

MSX-H38

180*

37

MSX-H42

216*

51

*Multiple media sections. Values represent total media width.

WARNING

Opening the manual supply valve will allow water to
pass to the media. Be sure the sump is safely draining
before opening the manual supply valve.

NOTE

The manual supply valve ships closed and must be
adjusted for proper performance.

NOTE

The recommended water pressure is based on media
width. Refer to the table provided for proper water
pressure settings.

Start-Up - Water Wizard™ (optional)

Program Display

NOTE

Steps 6 through 8 are provided to adjust the minimum
cooling temperature. The minimum cooling is preset
to the factory recommended 75°F (24°C). Only adjust
if needed.

NOTE

The inlet air sensor function overrides and shuts down
the evaporative cooler if the outside temperature falls
below the minimum cooling temperature.

7. Adjust the Minimum Cooling Temperature.

While in the Program Menu, use the Up and Down
Keys to navigate the Menu Options until “toF” is
displayed. Press the Enter Key

to access the

selected Menu Option setting.

Use the Up and Down Keys to adjust the Minimum

Cooling Temperature as needed. Press the Enter
Key

to save the Minimum Cooling Temperature

setting and return to the Program Menu.

Minimum Cooling

Temperature Display

NOTE

The enter key

must be pressed to save the new

minimum cooling temperature.

5. Check Media. Start the cooling cycle and check

the media after one hour of operation. If the media
is continuously dry or if too much water is draining
from the sump tank, refer to Troubleshooting, Water
Wizard™.

6. Enter Program Mode. Press and hold the Enter

Key

for three seconds. The display will read

“Pro” when Program Mode is active.

Function Key

L1

L2

L3

Enter Key

Up Key

Down Key

1. Open the Solenoid. Confirm that the manual

water supply valve is closed. Press and hold the
Function Button

for one second. L3 will begin

blinking (short on, long off), indicating that Flow
Test Mode is active and the supply solenoid is
open.

2. Set the Water Pressure. With the solenoid open,

set the supply water pressure to the correct setting
(see table below). Use the manual supply valve to
adjust the supply pressure. A pressure gauge is
provided between the manual supply valve and the
media.

3. Break-in Media. Leave the supply solenoid open

to saturate and break-in media for 20 minutes with
the blower off.

4. Close Solenoid. With the pressure set, press the

Function Key

for one second to deactivate

Flow Test Mode and allow the supply solenoid to
close.