beautypg.com

Troubleshooting, Too much airflow, Insufficient airflow – Greenheck MSX (470658) User Manual

Page 29

background image

29

Modular Supply Make-Up Air Unit

®

Troubleshooting

Too Much Airflow

Blower speed too high?

Adjust drives as needed.

(Reference Blower Start-Up Step #5)

Insufficient external static

pressure?

Increase external static pressure.

Filters not in place?

Install filters.

Yes

Yes

Yes

No

No

Everything is working properly,

consult factory.

No

Insufficient Airflow

Damper(s) not fully opened?

Filters dirty or clogged

Blower speed too low?

System static losses too high?

Yes

Yes

Yes

Yes

No

No

No

No

No

Leaks in ductwork

Yes

Belt slipping

Yes

Everything is working properly,

consult factory.

Yes

Adjust damper linkage(s), or replace faulty actuator(s).

(Damper actuators may take a few minutes to open)

Clean or replace filters.

(Reference Filter Maintenance in the Maintenance section).

Adjust drives as needed.

(Reference Blower Start-Up Step #5)

Reduce losses by improving ductwork.

Repair leaks.

Replace or tighten belt.

(Reference V-Belt Maintenance in the Maintenance section)