Modular Supply Make-Up Air Unit

®

Installation of Water Wizard

TM

(optional)

Evaporative Cooling with the Water Wizard™

1. Install Normally Closed Supply Line/Solenoid.

Connect the water supply line to the manual supply
valve in the unit. Install the supply solenoid in the
supply line, upstream of the manual supply valve and
below the roof line.

2. Install Normally Open Drain Line/Solenoid.

Connect the drain line to the supply line between the
manual supply valve and the supply solenoid. Install
a drain solenoid in the drain line, below the roof line.
A trap should be installed in the drain line.

3. Wire the Solenoid(s). Wire the supply line solenoid

and drain solenoid as shown on the unit’s wiring
diagram in the control center.

4. Wire the Temperature Sensor. If the evaporative

cooler shipped separate from the unit, the
temperature sensor must be wired. The sensor
wire is bundled inside the discharge end of the
evaporative cooler. Wire the sensor wire to terminals
as shown on the unit’s wiring diagram.

NOTE

The following instructions are provided for evaporative
coolers equipped with the Water Wizard™ only.
Additional instructions are provided for evaporative
coolers equipped with the auto-drain and fill or bleed-off.

WARNING

Disconnect and lock-out all power and gas before
performing any maintenance or service to the unit.
Failure to do so could result in serious injury or death
and damage to equipment.

NOTE

Solenoid(s) may be provided by Manufacturer (if
ordered) or by others.

CAUTION

Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.

NOTE

The Water Wizard™ start-up must be completed for
proper performance.

Water Wizard™ Valves

(When provided by Manufacturer)

Unit

Model

Assembly

Number

Mfg.

Part

No.

ASCO

Part No.

Solenoid

Type

De-

Energized

Position

Diameter Qty.

MSX -

H12/H22

MSX - H32

(<9000 cfm)

852370

461262 8210G2 Supply Closed

1/2 inch

(12.7 mm)

1

383086 8210G34

Supply

Line

Drain

Open

1/2 inch

(12.7 mm)

1

MSX - H32

(≥9000 cfm)

MSX-H35,

H38, H42

852371

383088 8210G9 Supply Closed

3/4 inch

(19.05 mm)

1

383086 8210G34

Supply

Line

Drain

Open

1/2 inch

(12.7 mm)

1

Part numbers subject to change.

Water Wizard™ Installation

Supply Line Drain Solenoid

(Normally Open)

Supply Solenoid

(Normally Closed)

Manual Supply

Valve

Pressure

Gauge

To Media

Sump Drain

Roof

Line

Trap

Field

Installed

Factory

Installed