beautypg.com

Troubleshooting, Motor overamps – Greenheck MSX (470658) User Manual

Page 28

background image

28

Modular Supply Make-Up Air Unit

®

Troubleshooting

Motor Overamps

Air volume too high?

Motor horsepower too low?

Motor voltage correct?

Blower rotation correct?

Actual static pressure

lower than design?

No

No

Yes

Yes

Yes

Yes

No

Yes

No

No

Shorted windings in motor?

Yes

Everything is working

properly, consult factory.

Yes

Adjust drives or increase external

static pressure as needed.

(Reference Blower Start-Up Step #5)

Resize motor.

Provide proper power supply.

(Reference Blower Start-Up Step #1)

Reverse blower rotation.

(Reference Blower Start-Up Step #2)

Adjust drives to reduce blower RPM.

(Reference Blower Start-Up Step #5)

Replace motor.