Installation of Direct Gas Piping

1. Determine the Supply Gas
Requirements

The unit’s direct gas nameplate states the
requirements for the gas being supplied to the unit.
The direct gas nameplate is located on the outside of
the unit on the control center side.

2. Install Additional Regulator if Required

When the supply gas pressure exceeds the maximum
gas pressure shown on the direct gas nameplate, an
additional regulator (by others) is required to reduce
the pressure. The regulator must have a listed leak
limiting device or it must be vented to the outdoors.

3. Connect the Supply Gas Line

A manual shut off valve (gas cock), 1/8 in. plugged
test port and 6 in. drip leg must be installed prior to
the gas train. The valve and the test port must be
accessible for the connection of a test gauge. Supply
gas connections must be made by a qualified installer
and are not furnished by manufacturer.

To

Controls

Gas Cock

From

Gas

Supply

6 in. Trap

1/8 in. Plugged Tap

Ground Joint Union

Supply Gas Line

NOTE

The regulator located inside the unit is used to
adjust the unit’s maximum output temperature.

Type of gas

“ W.C.

“ W.C.

“ W.C.

F

PSI

“ W.C.

“ W.C.

MAX BTU/HR
BTU/H MAX

NORMAL MANIFOLD
PRESSURE
PRESSION DÕADMISSION
NORMALE

MIN GAS
PRESSURE
PRESSION DE GAZ

MIN BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR

TYPE OF GAS
NATURE DU GAZ

MIN BTU/HR
BTU/H MIN

MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX

MAX BURNER
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR

MAX GAS
PRESSURE
PRESSION DE GAZ
MAX

DESIGN ∆T
∆T NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“ W.C.

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

Maximum gas pressure

Minimum gas pressure for
maximum output

Direct Gas Nameplate

IMPORTANT

All gas piping must be installed in accordance
with the latest edition of the National Fuel Gas
Code ANSI/Z223.1 and any local codes that may
apply. In Canada, the equipment shall be installed
in accordance with the Installation Code for Gas
Burning Appliances and Equipment (CGA B149)
and Provincial Regulations for the class. Authorities
having jurisdiction should be consulted before
installations are made.

WARNING

All components of this or any other gas-fired heating
unit must be leak tested prior to placing the unit
into operation. A soap and water solution should be
used to perform this test. NEVER test for gas leaks
with an open flame.

WARNING

When leak testing pressures that are equal to
14 in. wc (3.5 kPa), first close the field-installed
shutoff valve to isolate the unit from the gas supply
line.

WARNING

When leak testing pressures that are above 14 in. wc
(3.5 kPa), close the field-installed shutoff valve,
disconnect the furnace and gas train from the gas
supply line and plug the supply line before testing.

IMPORTANT

All piping should be clean and free of any foreign
matter. Foreign material entering the gas train can
damage the valves, regulators and burner.

IMPORTANT

Do NOT connect the unit to gas types other than
what is specified and do NOT connect the unit to
gas pressures that are outside of the pressure range
shown on the label.

NOTE

When connecting the gas supply, the length of the
run must be considered in determining the pipe size
to avoid excessive pressure drop. Refer to a Gas
Engineer’s Handbook for gas pipe capacities.