beautypg.com

Start-up - water wizard™ (optional), Exit program mode, Adjust the minimum cooling temperature – Greenheck DG/DGX Pilot Ignition (470651_IOM) User Manual

Page 20: Close solenoid, Check media, Open the solenoid, Set the water pressure, Enter program mode, Break-in media

background image

NOTE

Steps 6 through 8 are provided to adjust the
minimum cooling temperature. The minimum cooling
is preset to the factory recommended 75ºF (24ºC).
Only adjust if needed.

NOTE

The inlet air sensor function overrides and shuts
down the evaporative cooler if the outside
temperature falls below the minimum cooling
temperature.

8. Exit Program Mode

After ten seconds of idle time the controller will exit
Program Mode.

7. Adjust the Minimum Cooling
Temperature

While in the
Program Menu,
use the Up and
Down keys to
navigate the
Menu Options
until “toF” is

displayed. Press the
Enter key to access the selected Menu Option setting.
Use the Up and Down keys to adjust the Minimum
Cooling Temperature as needed. Press the Enter key
to save the Minimum Cooling Temperature setting and
return to the Program Menu.

Minimum Cooling

Temperature Display

NOTE

The enter key must be pressed to save the new
minimum cooling temperature.

Start-Up - Water Wizard™ (optional)

4. Close Solenoid

With the pressure set, press the Function key
for one second to deactivate Flow Test Mode

and allow the supply solenoid to close.

5. Check Media

Start the cooling cycle and check the media after one
hour of operation. If the media is continuously dry or if
too much water is draining from the sump tank, refer
to Troubleshooting, Water Wizard™.

NOTE

The recommended water pressure is based on
media width. Refer to the table provided for proper
water pressure settings.

1. Open the Solenoid

Confirm that the manual water supply valve
is closed. Press and hold the Function key

for one second. L3 will begin blinking (short on, long
off), indicating that Flow Test Mode is active and the
supply solenoid is open.

2. Set the Water Pressure

With the solenoid open, set the supply
water pressure to the correct setting from

the following tables. Use the manual supply valve
to adjust the supply pressure. A pressure gauge is
provided between the manual supply valve and the
media.

WARNING

Opening the manual supply valve will allow water
to pass to the media. Be sure the sump is safely
draining before opening the manual supply valve.

NOTE

The manual supply valve ships closed and must be
adjusted for proper performance.

Recommended Water Pressure Chart

Housing

Size

Media Width

(inches)

Water Pressure

(in. wg)

DG-10

26

3

4

19

DG-20

66

74

DG-30

84*

35

DGX-12

30

20

DGX-22

43

3

4

36

60

61

DGX-32

66

72

96*

42

DGX-35

120*

61

DGX-38

180*

37

DGX-42

216*

51

*Multiple media sections. Values represent total media width.

Program Display

6. Enter Program Mode

Press and hold
the Enter key

for three seconds. The
display will read “Pro”
when Program Mode is
active.

Function

L1

L2

L3

Enter

Up
Down

Water Wizard™ User Interface

Key Function Description

3. Break-In Media

Leave the supply solenoid open to saturate and
break-in media for 20 minutes with the blower off.

Model DG / DGX Pilot Ignition Make-Up Air

20

®