NOTE

The Freeze Temperature is preset to the factory
recommended 45ºF. Steps 9-11 should only
be completed if the Freeze Temperature needs
adjustment.

NOTE

The Freeze Temperature is the temperature at which
the supply solenoid closes and the drain solenoid
opens to drain the supply line, preventing possible
freeze damage. A drain solenoid is required for this
option.

9. Enter Program Mode

Press and hold
the Enter key

for three seconds. The
display will read “Pro”
when Program Mode is
active.

10. Adjust the Freeze Temperature

While in Program Mode, use the Up and Down
keys to navigate
through the
Menu Options
until “Frt” is
displayed. Press

the Enter key to access
the selected Menu
Option setting.
Use the Up and Down keys to adjust the Freeze
Temperature setting as needed. Press the Enter key to
set the Freeze Temperature and return to the Program
Menu.

Program Display

Freeze Temperature

Display

NOTE

The enter key must be pressed to save the new
freeze temperature.

Program Mode

Program Mode allows the user to view the Program
Menu and edit the factory default settings. To access
Program Mode and view the Program Menu, press
and hold the Enter key for three seconds. While
viewing the Program Menu, press the Up and Down
keys to scroll through the Menu Options. To view
the setting of the selected Menu Option, press the
Enter key. To edit the setting, press the Up or Down
key while viewing the setting. To save the setting
and return to the Program Menu, press the Enter key.
To return to the Program Menu without saving the
change, wait 10 seconds. To exit Program Mode from
the Program Menu, wait 10 seconds.

Operation - Water Wizard™ (optional)

CAUTION

The sump drain line must be clear and draining to a
safe location before using Flow Test Mode.

CAUTION

Be aware of the water level in the sump tank at all
times when using the Flow Test Mode.

WARNING

Changing the default settings will significantly affect
performance. Only change a setting after reading
and understanding this entire manual.

WARNING

The Enter key must be pressed to save any changes
made to a setting.

Light Status

Indicating

Light

On

Off

Blinking

Long on, short off

Blinking

Short on, long off

L1

Call for

cooling

No

call for

cooling

Call for cooling.

Outdoor

temperature

lockout.

N/A

L2

Drain

solenoid

open

Drain

solenoid

closed

N/A

Supply solenoid

open. (Drain

solenoid closed).

L3

Cooling

on

Cooling

off

Supply solenoid

locked closed

Flow test

mode active

Drain Mode

locks open the drain solenoid and

drains the supply line between the supply solenoid
and the media. To activate Drain Mode simultaneously,
press the Function and Enter keys (L2 will light). To
deactivate Drain Mode and unlock the drain solenoid,
simultaneously press the Function and Enter keys
again.

Flow Test Mode

- Activating Flow Test Mode

opens the supply solenoid and allows water to pass to
the manual supply valve. To activate Flow Test Mode,
press and hold the Function key for one second (L3
will flash). To deactivate Flow Test Mode and allow the
supply solenoid to close, press and hold the Function
key again for one second.

Dry Bulb Temperature

The dry bulb temperature is visible on the home
screen. If a number is not visible, wait 15 seconds
and use the Up and Down keys until a number is
displayed.

Wet Bulb Temperature

To view the Wet Bulb Temperature, simultaneously
press and hold the Up and Down keys.

Indicating Lights

Three indicating lights are located across the top
of the display to indicate the status of the Water
Wizard™.

11. Exit Program Mode

After ten seconds of idle time the controller will exit
Program Mode.

Model DG / DGX Pilot Ignition Make-Up Air

21

®