Table of Contents

Installation

Clearance to Combustibles/Service Clearances . 3

Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Unit Arrangement DB / HZ / UB . . . . . . . . . . . . . . 4

Roof Mounted Unit — Arrangement DBC . . . . . . 5

Optional Evaporative Cooling Module . . . . . . . . . 6

Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Direct Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . 8

Optional Evaporative Cooler Piping . . . . . . . . . . . 9

Optional Water Wizard™ . . . . . . . . . . . . . . . . . . 11

Optional Direct Expansion (DX) Coil Piping . . . . 12

Optional Chilled Water Coil Piping . . . . . . . . . . . 13

Optional Building Pressure Control . . . . . . . . . . 14

Start-Up

Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Direct Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Optional Evaporative Cooling Recirculating . . . 19

Optional Water Wizard™ . . . . . . . . . . . . . . . . . . 20

Operation

Optional Water Wizard™ . . . . . . . . . . . . . . . . . . 21

Optional VAV Units . . . . . . . . . . . . . . . . . . . . . . . 22

Optional Recirculating Units . . . . . . . . . . . . . . . . 23

Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Troubleshooting

Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Motor Overamps . . . . . . . . . . . . . . . . . . . . . . . . . 26

Insufficient / Too Much Airflow . . . . . . . . . . . . . . 27

Excessive Noise or Vibration . . . . . . . . . . . . . . . 28

Direct Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Optional Evaporative Cooling . . . . . . . . . . . . . . . 32

Optional Water Wizard™ . . . . . . . . . . . . . . . . . . 33

Maintenance

Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Fall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Reference

Gas Train Layouts . . . . . . . . . . . . . . . . . . . . . . . . 37

Control Center Layout / Dirty Filter Switch . . . . 38

Start-Up Check List . . . . . . . . . . . . . . . . . . . . . . 39

Maintenance Log . . . . . . . . . . . . . . . . . .Backcover

Warranty . . . . . . . . . . . . . . . . . . . . . . . . .Backcover

Clearance to Combustibles /

Service Clearances

Floor

Top

Sides

Ends

Insulated/

Units

0 inches

(0 mm)

0 inches

(0 mm)

0 inches

(0 mm)

0 inches

(0 mm)

Non Insulated

Units

0 inches

(0 mm)

6 inches

(152.4 mm)

6 inches

(152.4 mm)

6 inches

(152.4 mm)

Clearance to combustibles is defined as the minimum distance
required between the heater and adjacent combustible surfaces
to ensure the adjacent surface’s temperature does not exceed 90
degrees above the ambient temperature.

Recommended Minimum Service Clearances

Housing 32 and less

42 inches (1066.8 mm)

on the controls side of the unit

Housing 35 and higher

48 inches (1219.2 mm)

on the controls side of the unit

Clearances for component removal (such as evaporative cooler
media) may be greater than the service clearances listed.

Installation of Indoor Unit

3. Seal Wall Opening

Apply sealant around
the perimeter of the
weatherhood to prevent
water penetration
and drafts into the
building.

1. Install Hangers

Install threaded hangers from ceiling supports. When
locating hangers, allow enough room to open access
panel(s). Two nuts must be used on the end of each
threaded hanger. Ceiling supports are supplied by
others.

2. Install Unit

Using sheet metal screws, attach the weatherhood/
thru-wall/filter section to the blower/burner section.
The flange on the weatherhood/thru-wall/filter section
should overlap the flange on the blower/burner
section.
Raise the assembled unit into place.
Using two nuts per hanger, fasten the unit supports to
the hangers under the unit. Appropriate unit supports,
such as the
optional
hanging
bracket
kit or
c-channel
and angle
iron
(supplied
by others)
should be
used.
Using self-tapping screws, attach ductwork to unit.
In order to prevent the unit from swinging and
to provide a safe environment for service and
maintenance, additional measures must be taken to
secure the unit in all directions.

NOTE

Two nuts must be used on each end of each
threaded hanging rod for proper support.

NOTE

Good duct practices should be followed for
all ductwork. Ductwork should be installed in
accordance with SMACNA and AMCA guidelines,
NFPA 96 and any local codes. Reference the CAPS
submittal for duct sizes.

Unit Supports

Ceiling Supports

Hangers

Ductwork

Indoor Mounting

Sealant

Seal Wall Opening

Model DG / DGX Pilot Ignition Make-Up Air