Installation of water wizard™ (optional), Install normally closed supply line/ solenoid, Install normally open drain line/ solenoid – Greenheck DG/DGX Pilot Ignition (470651_IOM) User Manual
Page 11: Wire the solenoid(s), Wire the temperature sensor, Evaporative cooling with the water wizard

Installation of Water Wizard™ (optional)
Evaporative Cooling with the Water Wizard™
1. Install Normally Closed Supply Line/
Solenoid
Connect the water supply line to the manual supply
valve in the unit. Install the supply solenoid in the
supply line, upstream of the manual supply valve and
below the roof line.
2. Install Normally Open Drain Line/
Solenoid
Connect the drain line to the supply line between the
manual supply valve and the supply solenoid. Install a
drain solenoid in the drain line, below the roof line. A
trap should be installed in the drain line.
3. Wire the Solenoid(s)
Wire the supply line solenoid and drain solenoid as
shown on the unit’s wiring diagram in the control
center.
4. Wire the Temperature Sensor
If the evaporative cooler shipped separate from the
unit, the temperature sensor must be wired. The
sensor wire is bundled inside the discharge end of the
evaporative cooler. Wire the sensor wire to the unit’s
control center. Refer to ladder diagram for proper
connections.
Water Wizard™ Installation
NOTE
The following instructions are provided for
evaporative coolers equipped with the Water
Wizard™ only. Additional instructions are provided
for evaporative coolers equipped with the auto-drain
and fill or bleed-off.
WARNING
Disconnect and lock-out all power and gas before
performing any maintenance or service to the unit.
Failure to do so could result in serious injury or
death and damage to equipment.
NOTE
Solenoid(s) may be provided by manufacturer (if
ordered) or by others.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
NOTE
The Water Wizard™ start-up must be completed for
proper performance.
Water Wizard™ Valves
(when provided by Manufacturer)
Unit
Model
Assm.
Number
Mfg.
Part
Number
ASCO
Part
Number
Solenoid
Type
De-Energized
Position
Diameter Qty.
DG-
H10/H20
DGX-
H12/H22
DGX-H32
(<9000 cfm)
852370
461262 8210G2 Supply
Closed
1/2 inch
(12.7 mm)
1
383086 8210G34
Supply
Line
Drain
Open
1/2 inch
(12.7 mm)
1
DG-H30
DGX-H32
(≥9000 cfm)
DGX-H35,
H38, H42
852371
383088 8210G9 Supply
Closed
3/4 inch
(19.05 mm)
1
383086 8210G34
Supply
Line
Drain
Open
1/2 inch
(12.7 mm)
1
Part numbers subject to change.
Sump Drain
To Media
Trap
Roof Line
Supply Line Drain Solenoid
(normally open)
Supply Solenoid
(normally closed)
Manual Supply Valve
Factory
Installed
Field
Installed
Pressure Gauge
Model DG / DGX Pilot Ignition Make-Up Air
11
®