Remote output switching (available with rtu only), Attaching the front cover – GAI-Tronics ICS Hazardous Area Page/Party Stations User Manual
Page 22

Pub. 42004-723L2G
ICS Hazardous Area Page/Party
®
Station
Page 20 of 31
f:\standard ioms - current release\42004 instr. manuals\42004-723l2g.doc
11/14
Page Disable Control
To disable local paging when the system VLC tone is present, set SW2-3 to the “on” position.
Remote Output Switching (Available with RTU Only)
To activate the RTU relay when the system VLC tone is present, set SW2-4 to the “on” position.
Attaching the Front Cover
After all adjustments have been completed, inspect and clean the machined flange joint surfaces of both
the cover and box. Surfaces must be smooth, free of nicks, scratches, dirt or any foreign particle build-up
that would prevent a proper seal. Surfaces must seat fully against each other to provide a proper
explosion-proof joint. Clean surfaces by wiping with a clean lint-free cloth.
Apply a light coat of Killark “LUBG” lubricant to flange surfaces and close the cover. Install and tighten
all cover bolts to 30 ft.-lbs. Make certain no cover bolts are omitted. Use only those bolts supplied with
the enclosure.
It may become necessary to re-terminate some or all of the enclosures in a system. If so, strip the wires
back to clean copper and connect only one wire to each connector to allow for easier future
troubleshooting.
N
OTE
: Refer to the Killark Installation, Operation, and Maintenance Data Sheet enclosed with the unit for
additional information.