ACC2500 Audio Control Center

Installation

25

09/08

Level Adjustments and Diagnostics

Programming Menu

The programming buttons,

PB1

through

PB4

, are used to navigate the menu for specific installations and to

perform diagnostics.

The diagram below illustrates which buttons to press to access the diagnostic menu features.

Press: To

select:

PB1

Line Output Adjust

Default: -10 dB

PB2

Line Input Sensitivity

Default: -9 dB

PB3

Internal Diagnostics:

Press:

To

select:

PB1

Relay Module Diag

PB2

Toggle Back-up Mode

PB3

RS-232 Diagnostic

PB4

Keyboard Diagnostic

PB4

Tone/Alarm Diagnostics

Press: To

select:

PB1

Sidetone Level Adjust (Default: 0 dBm)

PB2

DTMF Level Adjust (Default: 0 dBm)

PB3

AMI Message Diagnostic

TIME

Set Current Time and Date

Reloading Factory Defaults

Desk sets are shipped from the factory with default settings that meet most installation requirements.
However, it is important to verify that these parameters are adjusted to meet your specific installation
needs.

To reload factory defaults, enter the Main Diagnostic Selection as described below. After entering this
mode, press

CTL

+

VOLUME

Up. The unit will automatically reset and show that the parameters are

corrupt. Follow the instructions on the display. For some models, this may happen twice.

N

OTE

: If your unit has been programmed with CARD Suite software, reloading the factory defaults will

reset all parameters that have been programmed.