Installation – Fronius IG 15 User Manual
Page 54

46
The FRONIUS IG unit can only be installed inside buildings or on outside
locations provided that they are protected from rain or snow.
- During certain operation phases the FRONIUS IG unit may develop a
slight noise level, for this reason it should not be installed in the immedi-
ate vicinity of living areas
- the FRONIUS IG unit is not to be set up in areas where there is heavy
dust development
- the FRONIUS IG unit is not to be set up in areas where there is heavy
incidence of conducting dust particles (for example iron filings)
- the FRONIUS IG unit is to be installed at a height which keeps the
display slightly below the position of your eyes in order to secure best
possible readability of the display.
- The distance between the top edge of the FRONIUS IG and the ceiling
should be approx. 30 cm.
Do not install the inverter in:
- areas with large amounts of dust
- areas with large amounts of conducting dust particles (e.g., iron filings)
- areas with corrosive gases, acids or salts
- areas where there is an increased risk of accidents, e.g., from farm
animals (horses, cattle, sheep, pigs, etc.)
- stables or adjoining areas
- storage areas for hay, straw, chaff, animal feed, fertilizers, etc.
Choosing the
location -
indoor hou-
sing
Installation
Make the best possible use of your FRONUS IG unit by additionally ob-
serving the following conditions:
- mains impedance should not be unnecessarily increased by a too nar-
row AC conductor cable cross section between the FRONIUS IG unit
and the in-house distribution panel. The AC conductor cable resistance
between the FRONIUS IG unit and the house distribution panel must
not exceed 0,5 Ohm.
- install it only on a solid vertical wall
- The ambient temperature should not be under minus 20 degrees or
over 50 degrees centigrade.
- No objects must be located within a distance of 15 cm around the air
vents on both sides of the FRONIUS IG unit
- Keep a lateral distance of 20 cm between individual FRONIUS IG units.
- The air flow direction within the inverter is from left to right (cold air
intake left, hot air exit right).
- When installing the FRONIUS IG unit in a switch panel cabinet (or
similar closed sections) it is necessary to make sure that the hot air
which develops will be discharged by forced ventilation.
Choosing the
location gene-
ral