7 view identification, 8 view torque profile – Flowserve MX Electronic Actuator User Manual
Page 93
![background image](https://www.manualsdir.com/files/784851/content/doc093.png)
93
Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
flowserve.com
5.7 View Identification
In this dialog, the identity of the actuator may be reviewed. This dialog provides valuable information for the ordering of
spare parts or checking the specification of the actuator.
NOTE: The serial number, order number, and software revision number were entered at the time of manufacture and
cannot be changed on screen. The software revision number is necessary when option boards are ordered.
Figure 5.6 – View identification
YES
YES
YES
NO
NO
YES
NO
NO
YES
NO
VIEW
IDENTIFICATION?
TAG #
MOV257
SERIAL #
M002567
ORDER #
366765F
FIRMWARE REV.
E654
YES
YES
NO
NO
YES
NO
YES
NO
VIEW NETWORK
REVISIONS?
YES
NO
DDC MODBUS
XXXXXXX
FF REV
XXXXXXXX
YES
NO
PROFIBUS DP
XXXXXXXX
PROFIBUS PA
XXXXXXXX
DEVICENET
XXXXXXXX
*Network revisions will only be displayed if the optional network board is installed within the MX.
*
*
*
*
-OK?
-OK?
-OK?
5.8 View Torque Profile
The information contained in the “TORQUE PROFILE” dialog provides indication of the condition of the valve relative to
the last time that the “DIAGNOSTIC RESET” reference values were reset. See Section 4.22, TAG Number. It can give an
indication of a change in the process conditions, such as an increase in pressure.
Details are given for the REFERENCE and the LAST torque, expressed as a percentage of the rated torque (stated on
the nameplate, Figure 4.7) that occurred at BREAKOUT, ENDING, and PEAK RUNNING for both the opening and closing
directions. Torque will be expressed proportionally as a reference only from 40% to 100% inclusive. Initial indication
may read 0% until torque exceeds 40% minimum.
• “BREAKOUT” – Amount of torque required to unseat the valve.
• “ENDING” – Amount of torque required to seat the valve.
• “PEAK RUNNING” – Maximum torque detected while cycling from BREAKOUT to ENDING. (Maximum mid-travel
torque.)
Figure 5.7 – View torque profile
YES
YES
YES
NO
NO
YES
YES
NO
NO
NO
YES
NO
YES
NO
YES
YES
YES
NO
NO
YES
YES
NO
NO
NO
YES
NO
YES
NO
YES
VIEW
O PEN D IRECTION?
B REAKOUT-REF
65(%)-NEXT?
BREAKOUT-LAST
70(%)-NEXT?
PEAK RUN
REF 40(%)-NEXT?
ENDING-LAST
40(%)-EXIT?
PEAK RUN
LAST 40(%)-NEXT?
ENDING - REF
40(%)-NEXT?
VIEW
CLOSE D IRECTION?
B REAKOUT-REF
40(%)-NEXT?
BREAKOUT-
LAST 43(%)-NEXT?
PEAK RUN
REF 40(%)-NEXT?
ENDING-LAST
60(%)-EXIT?
PEAK RUN
LAST 40(%)-NEXT?
ENDING-REF
55(%)-NEXT?
VIEW
TORQUE PROFILE