Flowserve MX Electronic Actuator User Manual
Page 90
Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
90
---% OPEN, TORQUE TIMEOUT – The torque switch timed out after the actuator determined that it has reached its
torque seat
“SET LIMITS” – Normal display if red selector knob is in “LOCAL” or “REMOTE” and position limits have not been set
“INITIALIZE” – “INITIALIZE” will be displayed if module has no actuator configuration. No operation will be permitted
until initialization has been completed. Refer to “ROM ERROR” for routine on next page. See Figure 5.1.
“ANALOG OUT 1 LOSS” – Analog board output-driver chip is reporting a fault, and cannot be reset; resulting in loss of
analog out signal.
“ANALOG OUT 2 LOSS” – Analog board output-driver chip is reporting a fault, and cannot be reset; resulting in loss of
analog out signal.
RAM Error
The MX processor continually checks RAM for memory corruption errors. If corruption is detected, the processor will
force a reset to clear RAM. The LCD will temporarily display the following prior to this reset:
“XXX% OPEN”
“RAM ERROR”
After the reset, the display will read normally. Any momentary commands (DDC command, momentary pushbutton,
etc.) that were not completely executed must be reissued.
ROM Error
The MX processor continually checks EPROM for memory corruption errors. If corruption is detected, operation is
disabled. If the selector switch is in “LOCAL” or “REMOTE,” the LCD will display the following:
“XXX% OPEN”
“ROM ERROR”
When the selector is placed in “STOP,” the unit will require reinitialization and the LCD will display the following dialog:
Figure 5.1 – Initialize routine
YES
NO
NO
YES
NO
YES
YES
YES
NO
NO
YES
NO
UNIT SIZE
MX-05-OK?
VOLTAGE
460 VOLT-OK?
Hz
60 Hz-OK?
ACTUATOR RP M
12/18-OK?
S/N
0------OK?
COLD (-60°C) UNIT
YES/NO -OK?
INITIALIZE?
Answer “
NO ” until the
correct unit size is
displayed. Refer to
nameplate.
Answer “
NO ” until
the correct voltage
is displayed. Refer
to nameplate.
Answer “
NO ” until
the correct frequency
is displayed. Refer to
nameplate.
Answer “
NO ” until
the correct rpm
is displayed. Refer
to nameplate.
Answer “
NO ” until the
value is displayed and
then “
YES ” to enter .
Refer to namplate for
S/N.
Answer “
NO” to
select normal
temperature
parameters,
-22°F to +158°F
(-30°C to +70°C).
Answer “
YES” to select arctic
temperature parameters,
-76°F to +140°F (-60°C to
+60°C).
Please refer to Limitorque
MX Customer Connection(s) Diagram
reverse side (located on the
inside of the terminal compartment
cover) for customer default
configuration.
Answer
“
NO” to
change.
Answer “
YES”
to save settings.
NO
YES