3 view diagnostics, 4 view hardware status – Flowserve MX Electronic Actuator User Manual
Page 91

91
Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
flowserve.com
5.3 View Diagnostics
A large amount of historical data is stored in the actuator memory and can be retrieved very easily, without the need for
password entry. The data is displayed in dialog format.
1. Enter the “SETUP” mode routine detailed in Section 2.1.1, Entering the Setup Mode.
2. Select “VIEW DIAGNOSTICS?”
3. Select “YES” to access the first display “VIEW HARDWARE?”
NOTE: It is recommended that ALL diagnostics information be recorded prior to contacting an authorized Limitorque
service coordinator at (434) 528-4400. This information aids in diagnosing any problem the actuator may experience.
Figure 5.2 – Diagnostic overview
5.4 View Hardware Status
Accessing the “VIEW HARDWARE” routine will enable some of the actuator components to be reviewed for their
integrity, as indicated below. These components are continuously being monitored.
Figure 5.3 – View hardware status
YES
NO
VIEW
DIAGNOSTICS?
YES
NO
NO
YES
NO
YES
NO
YES
NO
VIEW
OPERATION LOG?
YES
NO
VIEW
QA DATA?
YES
NO
YES
NO
YES
VIEW
HARDWARE?
VIEW
ERROR CODE?
VIEW
MOTOR STATUS?
VIEW
POWER SUPPLY?
VIEW
IDENTIFICATION?
VIEW
TORQUE PROFILE?
YES
NO
VIEW
QA DATA?
YES
NO
QA STAMP
V#87654321-OK?
YES
NO
QA DATE
01 AUG 2013?
YES
NO
QA TIME
12:32:45
YES
YES
YES
NO
NO
YES
NO
“
NO ” toggles options
??? (Analog input present
0-100%)
OP (Open input present)
CL (Close input present)
STOP (Stop input present)
ESD (ESD input present)
IO (Open inhibit input present)
IC (Close inhibit input present)
YES
NO
YES
NO
(See NOTE 1)
YES
NOTE 1: If ordered.
NOTE 2: Reserved for future.
LimiGard functionality
through monitor relay.
(See NOTE 1)
VIEW
HARDWARE
THERMISTOR
(OK)-NEXT?
ENCODER
(OK)-NEXT?
I/O OPTION
(OK)-NEXT?
POWER BOARD
(OK)-NEXT?
DDC
(OK)-NEXT?
NO
(See NOTE 1)
NO
(See NOTE 2)
LIMIGARD
(OK)-NEXT?
YES
A = ???
NO
FF
(OK)-NEXT?
YES
NO
TORQUE SENSOR
(OK)-NEXT?
YES
NO
YES
(See NOTE 1)
PB/DP
(OK)-NEXT?
NO
(See NOTE 1)
PB/PA
(OK)-NEXT?
YES
NO
DEVICENET
(OK)-NEXT?
(See NOTE 1)