Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
flowserve.com
Input 3 (normal default - stop) terminal 26:
• Set as enabled, ESD release function, signal absent = active
Input 4 (normal default - open) terminal 25:
• Set as enabled, ESD Release function, signal present = active
Input 5 (normal default - close) terminal 27:
• Set as enabled, momentary ESD/PSESD function, signal present> 800 ms = active, ESD action =
Close, partial stroke target position = 0% open The ESD release signals are setup as redundant signals for safety. There
are two signal inputs, and BOTH must be in the active state. If there is an active ESD and both ESD release inputs are in
the active state, the ESD will be unlatched and the unit will return to normal operation. If the ESD release inputs are in
a fault state, an active ESD will NOT be released. The ESD release inputs will have no effect on a partial stroke ESD test.
The momentary ESD/PSESD input will be ignored if there is a signal present for less than 100 ms, and is guaranteed to
latch in the ESD/PSESD if the signal is present for greater than 800 ms. Once the ESD is latched in, the unit will perform
the ESD action. In this case the ESD will move the unit to the close limit and remain in ESD mode until the ESD release
indication is given using the ESD release inputs.
Figure 4.33 – SIL control (Enhanced)
SIL CONTROL
ENHANCED?
STATUS
(OFF)-OK?
STATUS
(OFF)-OK?
STATUS FUNC
USER INPUT-OK?
SIGNAL
PRESENT-OK?
CHANGE
OUTPUT 0?
CHANGE
INPUT-0?
VIEW
DIAGNOSTICS?
YES AND
2 WIRE
OPEN INHIBIT
CLOSE INHIBIT
BOTH INHIBIT
2-WIRE OPEN
2-WIRE CLOSE
NOTES:
NOTE 1: 2 Wire controls are not selectable is DDC, PBCP, PBPA,
Devicenet, FF, or Maclulating controls are enabled.
SEE NOTE 1
YES AND
NOT 2 WIRE
SEE NOTE 1
ABSENT
YES AND NOT POSITION
IGNORE
CLOSE
OPEN
STOP
YES
YES
YES
OFF
YES
YES
YES
YES
YES
YES
YES
ABSENT
NO
NO
NO
NO
STATUS FUNC USER
MO ESD/PSESO-OK?
NO
SIGNAL
PRESENT-OK?
NO
ESD ACTION
POSITION-OK?
NO
ESD MORE TO
XXX%-OK?
NO
PROP BAND
XXX%-OK?
NO
DEAD BAND
XXX%-OK?
NO
PS MOVE TO
XXX%-OK?
NO
YES