Flowserve MX Electronic Actuator User Manual
Page 70
Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
70
4.18.2 Inhibit
Default = INHIBIT>ESD
To Customize the Settings:
Select “NO” to choose:
• “ESD>INHIBIT” – ESD overrides active inhibit signal
• “INHIBIT>ESD” – Active inhibit signal will override ESD
NOTE: Removing the wires to these terminals can disable active inhibits.
4.18.3 Local Command
Default = LOCAL>ESD
To Customize the Settings:
Select “NO” to choose:
• “ESD>LOCAL” – ESD overrides local command to operate actuator
• “LOCAL>ESD” – Local command to operate actuator overrides ESD
4.18.4 Stop
Default = STOP>ESD
To Customize the Settings:
Select “NO” to choose:
• “ESD>STOP” – ESD overrides stop command
• “STOP>ESD” – Stop command overrides ESD
4.18.5 Jammed Valve*
Default = JAMMED VALVE>ESD
To Customize the Settings:
Select “NO” to choose:
• “ESD>JAMMED VALVE” – ESD overrides jammed valve indication
• “JAMMED VALVE>ESD” – Jammed valve indication overrides ESD (default)
* See CAUTION on Figure 4.24.
4.18.6 Lost Phase*
Default = LOST PHASE>ESD
To Customize the Settings:
Select “NO” to choose:
• “ESD>LOST PHASE” – ESD overrides lost phase indication
• “LOST PHASE>ESD” – Lost phase indication overrides ESD
* See CAUTION on Figure 4.24.