4 remote control, 5 local indication – Flowserve MX Electronic Actuator User Manual
Page 38

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
38
3.6.4 Remote Control
Once the position limits have been set, and “REMOTE” mode is enabled:
1. Place the red selector knob in “REMOTE” to permit command control by a remote device. Local “OPEN/CLOSE”
mode will be prevented.
2. Rotating the red selector knob to the “STOP” position will automatically stop the actuator regardless of the remote
control signal unless ESD override has been selected. See Section 4.18, ESD (Emergency Shutdown) Overrides.
The red selector knob may be locked in or out of any of its three positions, “LOCAL/STOP/REMOTE,” using a padlock. A
1/4 inch padlock is recommended.
The LCD displays status and valve position. In normal operation mode, the top line displays “XXX % OPEN,” while the
bottom line displays “STATUS OK.” Refer to Section 4.13, Status and Alarm Contacts for a list of “ALARM” or “STATUS
MESSAGES.” Table 3.9 details the LED indicators’ default settings.
3.6.5 Local Indication
Figure 3.25 – Control panel
CLOSE
STOP
OPEN
(YES)
REMOTE
LOCAL
(NO
)
Red selector knob
Black selector knob
Red
Yellow
Blue
Green
Table 3.9 – LED indicators – default settings
LED Indicator
Operation Description
Yellow
Red
Green
OFF
ON
OFF
Valve is fully open
(Red knob in “REMOTE”)
OFF
OFF
ON
Valve is fully close
(Red knob in “REMOTE”)
OFF
OFF
Blinking Valve is closing (Red knob in “REMOTE”)
OFF
Blinking
OFF
Valve is opening (Red knob in “REMOTE”)
ON
OFF
OFF
Actuator in“REMOTE” and stopped in
mid-travel
Blinking
OFF
OFF
Monitor relay alarm or actuator (red knob)
in “LOCAL” or “STOP”
Red and green LED indicators can be reversed. See Section 4.17, Local Control.
NOTE: The blue LED indicator is supplied to indicate optional Bluetooth availability in the MX. This LED will light when