6 proportional band, 7 deadband, 8 comm loss delay – Flowserve MX Electronic Actuator User Manual
Page 58: 9 comm loss action

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13
58
4.12.6 Proportional Band
Proportional band is the range of errors between position and demand signal that will produce reduced speed (pulsing).
Default = 15%
To change from the default, select “NO” until the required value is displayed. The value is adjustable between 1% and
100%, in 1% increments.
4.12.7 Deadband
Default = 2%
The deadband should be wide enough to prevent “hunting” of the actuator but as low as possible to give adequate
response to changes in the error signal.
To Change from the Default Range:
Select “NO” to adjust the value between 1% and 50%, in 1% increments to suit the application.
Figure 4.17 – DN option
DNET ADDRESS
NET CTRL-OK?
ANALOG SCALE
(0-100)-OK
* If POSITION is chosen, as action,
this menu will appear.
YES
NO
(ON)
YES
NO
(CLOSE)
(OPEN)
(STOP)
(POSITION)
YES
NO
ESD ACTION
(IGNORE)-OK?
(CLOSE)
(OPEN)
(STOP)
(POSITION)
YES
NO
COMM LOSS ACTION
(NONE)-OK?
(0-4095)
YES
NO
(ASCII)
YES
NO
(0-100%)
*
*
YES
NO
MOVE TO
XXX% OPEN
(0-100%)
YES
NO
MOVE TO
XXX% OPEN
(2400-115.2K)
YES
NO
(1-250)
YES
NO
YES
NO
CHANGE PROP
DEAD BAND?
(1-100%)
YES
NO
PROP BAND
(8%)-OK?
(1-?%)
YES
NO
DEADBAND
(2%)
CHANGE
DEVICENET?
STATUS
(OFF)-OK?
BAUD RATE
AUTO-OK?
COMM LOSS DELAY
(60 SEC)-OK?
4.12.8 Comm Loss Delay
Default = 60 sec.
The User may select the amount of time delay before communication loss is flagged to the network. This selection is
configurable from 120 seconds.
4.12.9 Comm Loss Action
Default = None
The User may select what action the actuator should take when network communication is interrupted. This action is
configurable as Close, Open, Stop, Position.