Maintenance, Safety instructions, Maintenance schedule – Flowserve Byron Jackson Type M User Manual
Page 50: 6 "maintenance, 6 maintenance 6.1 safety instructions, 2 maintenance schedule

®
Byron Jackson Double Mechanical Seal Submersible Pumping Unit • 1042.293/9 • June
04
Page 50 of 68
6 MAINTENANCE
6.1 Safety
instructions
Before maintenance or repair work
DANGER
Before commissioning, operation or
shutdown of the pumping unit, read
Chapter 1.6 "Safety", Page 6.
Before starting any maintenance or
repair work or removing any parts of
the pumping unit:
1. Switch off the motor, see Chap-
ter 5.5 "Stopping and shutdown",
Page 49.
2. Completely separate the pump-
ing unit from the power supply.
During maintenance or repair work
During maintenance or repair work, avoid polluting
water or soil with hazardous substances such as
lubricants or cleaning agents. Collect these sub-
stances in suitable containers and dispose of the in
accordance with the local regulations.
After maintenance or repair work
Immediately after finishing maintenance or repair
work and before restarting the pumping unit, en-
sure that
•
all tools and equipment required for mainte-
nance or repair work have been removed from
the pumping unit
•
all screws and connections that were previ-
ously undone are retightened
•
all safety devices are replaced and/or operate
correctly
•
the motor is filled.
6.2 Maintenance
schedule
NOTE Not all components or sub-
assemblies of a pumping unit are
necessarily supplied by Flowserve
or part of this delivery.
These user instructions apply only
to the components or sub-
assemblies supplied by Flowserve
in this delivery, see Chapter 12.1
"Scope of delivery".
Flowserve submersible pumps are custom de-
signed to operate for extended periods with a
minimum of regular maintenance, the frequency
and scope of maintenance depending primarily on
the conditions of service to which the pump is sub-
ject. Periodic dismantling for inspection is not nec-
essary unless excessive wear is indicated or a
pump malfunction is suspected.
To determine when major maintenance is required,
periodic testing of the pumping unit (as described
in Chapter 6.7 "Periodic testing", Page 52) is
strongly recommended. This will establish a base-
line of performance data indicative on pump condi-
tion that will permit scheduling of major mainte-
nance tasks well ahead of the time they become
necessary and will prove very beneficial to the pro-
longed lift and satisfactory operation of the pump-
ing unit.
Interval Part
Maintenance
All parts
Inspect all piping connections for evidence of leakage, loosening or
other damage and repair if necessary.
Before each installation and after
each uninstallation
Pump bowl assembly Inspect the integrity of the pump mounting fasteners which may loosen
due to vibration, and tighten if necessary.
Motor
Periodic testing, see Chapter 6.7, Page 52.
Every 2 - 3 months
Power cable, motor
Electrical tests of the motor, see Chapter 6.8, Page 53.
Every 2 to 3 months if pump stands
idle for longer period of time
Pump bowl assembly
Pump test run, see Chapter 6.6, Page 51.
Table 7
Maintenance schedule