Delta Temperature Controller User Manual
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED - 17 -
2007-09-17
Display
Explanations
PV
SV
Status of the temperature controller
The control modes include: ON/OFF, MANUAL, PID and PID
PROG. Default = PID. Select “MANUAL” here.
Back to
top
Press
to return to the main screen.
Parameters relevant to MANUAL control
Press
in the main screen of DTB to enter the “regulation mode”.
Display
Explanations
PV
SV
Status of the temperature controller
or
Set up heating or cooling control cycle. Default = heating, 20
seconds per cycle.
Press
in the main screen of DTB to enter the “operation mode”.
Display
Explanations
PV
SV
Status of the temperature controller
Run/stop
Set up the position of decimal point.
1 = value with decimal point; 2 = value without decimal point
Key-locked function
Manually adjust the output percentage. Assume the percentage
value = 50 and the cycle = 20 seconds plus heating control, the
system will conduct heating output for 10 seconds and stop for
the other 10 seconds.
3.3 PID
Press
for 3 seconds in the main screen to enter the “initial setting mode”. Press
several
times until the parameter
is displayed.
Display
Explanations
PV
SV
Status of the temperature controller
The control modes include: ON/OFF, MANUAL, PID and PID PROG.
Default = PID.
Back to
top
Press
to return to the main screen.
Parameters relevant to PID control
Press
in the main screen of DTB to enter the “regulation mode”.