5.1.5 Private Managed Objects

MIBs for Contemporary Controls — 1.3.6.1.4.1.17384

Switch Family — 1.3.6.1.4.1.17384.1

Switch Series — 1.3.6.1.4.1.17384.1.1

oid = “1.3.6.1.4.1.17384.1.1.1.0”

temperature: indicates the internal temperature of the switch in degrees Celsius.

Type: string

Access: read-only

5.1.5.1 Relay Group – 1.3.6.1.4.1.17384.1.1.2

oid = "1.3.6.1.4.1.17384.1.1.2.1.0"

switchFaultStatus: the fault status of this switch.

Type: integer

1 = fault has occurred

2 = no fault has occurred

Access: read-only

5.1.5.1.1 Fault Table – ‘faultTable’ 1.3.6.1.4.1.17384.1.1.2.2

oid = "1.3.6.1.4.1.17384.1.1.2.2.1.ifIndex"

portMonitoringFaultStatus: fault status for each port.

Type: integer

1 = fault has occurred

2 = no fault has occurred

Access: read-only

5.1.5.2 RapidRing Group – 1.3.6.1.4.1.17384.1.1.3

oid = “1.3.6.1.4.1.17384.1.1.3.1.0”

ringEnableStatus: the RapidRing is enabled or disabled

Type: integer

1 = RapidRing is enabled

2 = RapidRing is disabled

oid = “1.3.6.1.4.1.17384.1.1.3.2.0”

switchMode: the switch is a Master or a Slave

Type: integer

1 = Master

2 = Slave

oid = “1.3.6.1.4.1.17384.1.1.3.3.0”

ringID: the group number of the RapidRing

Type: integer

1 = group number 1

2 = group number 2

oid = “1.3.6.1.4.1.17384.1.1.3.4.0”

networkStatus: the network topology

Type: integer

1 = Ring Not Available (because RapidRing is not enabled)

2 = Ring Complete

3 = Ring Incomplete