DeviceNet interface 

 

 

 

9.17.026 

 
 

12.1.3 DeviceNet error description 

 

SITUATION 

Description 

Minor communication error 
(red LED: 0.1 sec on, 2 sec off) 

Each communication error will be seen as a minor communication error 
except for when the instrument is in the communication fault state. 
Instrument will stay in the on‐line state. These errors will be recovered 
automatically. 
Examples of minor errors: 
When instrument is only member on DeviceNet network 
When an I/O connection time‐out has occurred 

No bus power 
(red LED: 0.2 sec on, 0.2 sec off) 

Instrument hardware detects that +24 Vdc in DeviceNet cable is not present.
 

Serious communication error 
( red LED: 2 sec on, 0.1 sec off) 

Instrument will get in communication fault state. This will happen at 
duplicate MAC ID or at bus‐off event (This node is faulty and is not allowed to 
have any influence on the bus). This state can only be left by manual 
intervention. Instrument needs a reset either by using the micro‐switch on 
top of the instrument or a new power‐up. At duplicate MAC ID situation, 
sending a new MAC ID via RS232 (e.g using FlowFix) could also solve the 
problem. 

 
 
 
 
 
 
 

12.2 T

ROUBLESHOOTING HINTS AND TIPS

 

 

SITUATION 

Description 

DeviceNet problems 

Check all DeviceNet settings at your master.  Master and device settings for 
use of memory modules must be the same. Make sure selected 
configuration at device configuration for polled I/O is the same as the 
settings at parameter data. See chapter 7 for more details. 
 
Check MAC ID and Baud rate of device (slave).  
 
Check cabling and bus termination of your DeviceNet system. 
 
Check power supply. Instruments need +24Vdc. 
 
Try to reset the instrument and/or restart your master. 
 
Make sure all settings for your slave are downloaded to your master 
(otherwise it won’t work). 
 
Contact DeviceNet sales representative or service department. 

Other (FLOW‐BUS) problems 

Contact Bronkhorst local sales representative or send e‐mail describing your 
problem to: see service chapter.