beautypg.com

Bronkhorst DeviceNet slave interface User Manual

Page 41

background image

BRONKHORST

®

 

Page 41   

 

 

 

 

DeviceNet interface 

 

 

 

9.17.026 

12.1.2 LED indications mode (MBC3 only) 

 

for this state 

Led 

Indication 

Network status LED (NET) 

Not powered/ Not 
online 

Off 

Device is not online

 The device has not been completed the Dup_MAC_ID test yet. 
 The device may not be powered, look at module status LED 
 No network power present 

Link OK, Online, 
Connected 

On 

 

 

 

green 

Device is online and has connections in the established state 

 For a group 2 device it means that the device is allocated to a master. 

Online, Not 
connected 

Flashing 

 

 

 

 

green 

0.5 sec on 

0.5 sec off 

The device is online but has no connections in the established state. 

 The device has passed the Dup_MAC_ID test, is online but has no 

established connections to other nodes 

 For a group 2 device it means that the device is not allocated to a master. 

Connection Time‐
out 
 

Flashing 

 

 

 

 

red 

0.5 sec on 

0.5 sec off 

One or more I/O connections are in timed‐out state.

Critical link Failure 

On 

 

 

 

red 

Failed communication device. The device has detected an error that has 
rendered it incapable of communicating on the network. (Duplicate MAC ID or 
bus off) 

Module status LED (MOD) 
No power 

Off 

There is no power applied to the device

Device operational 

On 

 

 

 

green 

The device is operating in normal condition.

Device in Standby 
(The device needs 
commissioning) 

Flashing 

 

 

 

green 

0.5 sec on 

0.5 sec off 

The device needs commissioning due to configuration missing, incomplete or 
incorrect. The device may be in the standby state. 

Unrecoverable fault 

On 

 

 

 

red 

The device has an unrecoverable fault, may need replacing. 

Device self testing 

Flashing 

red / green 

0.5 sec on 

0.5 sec off 

The device is in self test. 

Module and status LED’s sequence at power‐up
Network LED (NET) 

off 

 

Module LED (MOD) 

 

 

 

green 

0.25 sec

Module LED (MOD) 

 

 

 

red 

0.25 sec

Module LED (MOD) 

 

 

 

green 

 

Network LED (NET) 

 

 

 

green 

0.25 sec

Network LED (NET) 

 

 

 

red 

0.25 sec

Network LED (NET) 

off 

 

 
 
 

 

 More information can be found in the manual “917023 Operational instructions digital instruments”
This document can be found at: 

http://www.bronkhorst.com/en/downloads/instruction_manuals/