3.3.7 S‐Single Stage Controller Object
Class Code 33 HEX
The S‐Single Stage Controller Object models a closed‐loop control system within a device.
CONTROLLER OBJECT’S INSTANCE ATTRIBUTES (Instance = 1)
SINGLE STAGE
CONTROLLER
OBJECT
ATTRI‐
BUTE
ATTRIBUTE NAME
SERVICE
CODE
DATA TYPE
FLOW‐
BUS
Comment
0x33
0x01
Number of
Attributes
0x0E
USINT
6
0x33
0x02
Attribute List
0x0E
Array of USINT
0x33
0x03
Data Type
0x0E, 0x10
USINT
0xC3=INT, 0xCA=REAL
0x33
0x04
Data Units
0x0E, 0x10
UINT
0x1001=counts, 0x1400=sccm, etc
0x33
0x05
Control Mode
0x0E, 0x10
USINT
0x33
0x06
Setpoint
0x0E, 0x10
INT or REAL
1
1,1
See attribute 3 and 4. For data unit
counts the setpoint attribute must be in
the range of 0..32000.
Where: 0 = min. setpoint (0%)
32000 = max. setpoint (100%)
0x33
0x0A
Status
0x0E
BYTE
0x33
0x13
Ramp Rate
0x0E, 0x10
UDINT
1,2
Setpoint slope in msec
(max. 3000000 msec)
1
Depends on the value assigned to the Data Type attribute. If the value of this attribute is 0xC3, the
selected data type is Integer, and if the value of this attribute is 0xCA, the selected data type will be the
IEEE‐754 single‐precision floating‐point.