4.4.2 Override 

The Override attribute is implemented as follows: 
 

Override 

Value to Valve

0 (Normal) 

set by attribute 6 (Actuator Value)

1 (Close) 

0

2 (Open) 

max. value

3 (Hold) 

last used value

4 (Safe state) 

See section 4.4.3.

 

4.4.3 Safe state 

In the following table the implemented values of the Valve output are shown. Mapping Safe state: 
 

Safe state 

Value to Valve

0 (zero/off) 

0

1 (full scale / on) 

max. value

2 (hold last value) 

last used value

3 (use safe value) 

Safe value (obj 0x32, attr 0x16)

 

4.5 G

AS CALIBRATION OBJECT INSTANCE

 

4.5.1 Gas standard number 

The  retrieval  of  the  gas  standard  number  is  implemented  as  follows:  the  first  2  characters  of  the  fluid  name  are 
interpreted as a decimal number. This number is returned as the gas standard number. 
 

4.5.2 Gas Symbol 

The fluid name is returned as the Gas Symbol. 
 

4.6 N

ETWORK ERROR DETECTION

 

When a network error is detected while the device is in Executing state, it is set back to the Idle or Critical Fault state. 
In those states the valve is set to the Safe state (see attribute Safe State in Analog Actuator object). When the device 
detects that no bus power is available, the network is closed and no communication is started until the bus power is 
detected again. 
 
Such errors are shown by the LED’s on the instrument. See the chapter “Troubleshooting”