beautypg.com

Bronkhorst DeviceNet slave interface User Manual

Page 20

background image

BRONKHORST

®

 

Page 20   

 

 

 

 

DeviceNet interface 

 

 

 

9.17.026 

Furthermore, with the use of the Data‐type attribute(0x03) and Data‐unit attribute(0x04) of the Sensor object 0x31 
and  the  Controller  object  0x33  the  user  can  select  one  of  the  following  settings  for  both  Explicit  and  Polled  I/O 
messages  (see  paragraph  3.2.2  for  a  complete  list  of  supported  data‐units,  the  settings  below  are  just  a  few 
examples): 
 

Example 1 (ClassId: 0x31, Data‐type: 0xC3, Data‐unit: 0x01 0x10):  

Signed Integer Count Indicated‐flow. 

Example 2 (ClassId: 0x31, Data‐type: 0xC3, Data‐unit: 0x00 0x14):  

Signed Integer SCCM Indicated‐flow. 

Example 3 (ClassId: 0x31, Data‐type: 0xCA, Data‐unit: 0x01 0x10):   Single‐precision floating‐point Count Indicated‐flow. 
Example 4 (ClassId: 0x31, Data‐type: 0xCA, Data‐unit: 0x00 0x14):   Single‐precision floating‐point SCCM Indicated‐flow. 
Example 5 (ClassId: 0x33, Data‐type: 0xC3, Data‐unit: 0x01 0x10):  

Signed Integer Count Setpoint. 

Example 6 (ClassId: 0x33, Data‐type: 0xC3, Data‐unit: 0x00 0x14):  

Signed Integer SCCM Setpoint. 

Example 7 (ClassId: 0x33, Data‐type: 0xCA, Data‐unit: 0x01 0x10):   Single‐precision floating‐point Count Setpoint. 
Example 8 (ClassId: 0x33, Data‐type: 0xCA, Data‐unit: 0x00 0x14):   Single‐precision floating‐point SCCM Setpoint. 

 
For Polled I/O messages only Data‐type can be selected.  The Data‐unit attribute will be automatically set when Polled 
I/O  is  started  (on  receipt  of  the  first  Polled  I/O  Request’s  Data).  The  Data‐unit  setting  will  be  determined  by  the 
selected IO Assembly Instance (see paragraph 2.5.1, Available data combinations for Polled I/O). 
 

 

The Data‐type and Data‐unit Attribute can only be set when the MFC is in the Idle state.  If the MFC is 
not in this state (i.e., Executing state) the user must use the Stop service (0x07) of Instance (0x01) of the 
Supervisor  object  (0x30)  to  allow  the  MFC  to  enter  the  Idle  state  for  making  the  change.  When  the 
attribute  has  been  set  the  user  can  use  the  Start  service  (0x06)  of  the  same  object  and  instance  to 
resume the Executing state. 


Example 1: 

How to program instrument with option 1 from above 

Object 

Instance  Service code  Attribute

Value

Description

30 

0x07 

stop: instrument to idle state;  
green LED long flash: 2 sec on, 0.1 sec off 

31 

0x10 

0x03

0xC3

Data type = INT

31 

0x10 

0x04

0x01 0x10

Data unit = COUNT

30 

0x06 

start: instrument to executing state green LED on 
continuously 


Example 2: 

How to program instrument with option 8 from above 

Object 

Instance  Service code  Attribute

Value

Description

30 

0x07 

 

stop: instrument to idle state; 
green LED short flash: 2 sec on, 0.1 sec off 

33 

0x10 

0x03

0xCA

Data type = REAL

33 

0x10 

0x04

0x00 0x14

Data unit = SCCM

30 

0x06 

start: instrument to executing state green LED on 
continuously