beautypg.com

4 changing slave address, baud rate and parity, Changing slave address, baud rate and parity – Bronkhorst LIQUI-FLOW mini (from 01-07-2013) User Manual

Page 26

background image

LIQUI-FLOW™ mini

9.17.065

Bronkhorst High-Tech BV

26

4.2.4

Changing slave address, baud rate and parity

Changing node address or baud rate by micro-switch operation

Press the micro-switch 5x briefly with intervals of max. 1 second in normal running/operation mode. Within the timeout period of

60 seconds it is possible to start changing the node address and baud rate of the instrument.

Step

Action

Indication

Time

Handling

1

Start

Press the switch 5x briefly with intervals of max. 1

second in normal running/operation mode.

2

Set tens of bus address

Green LED flashes

0.1 sec on, 0.1 sec off

count flashes

start when switch

is pressed:

0.5 sec on, 0.5 sec off

timeout:

60 sec

Press switch and count green flashes for tens of

bus address.

Release when wanted amount has been count.

Counts up to max. 12 and than starts at 0 again.

When counting fails, keep switch pressed and

restart counting for next attempt.

3

Set units of bus address

red LED flashes

0.1 sec on, 0.1 sec off

count flashes

start when switch

is pressed:

0.5 sec on, 0.5 sec off

timeout:

60 sec

Press switch and count red flashes for units of bus

address.

Release when wanted amount has been count.

Counts up to max. 9 and than starts at 0 again.

When counting failed, keep switch pressed and

restart counting for next attempt.

4

Set baud rate of field

bus communication.

1 = 9600 Baud

2 = 19200 Baud

3 = 38400 Baud

4 = 56000 Baud

5 = 57600 Baud

6 = 115200 Baud

both red and

green LEDs flashes

0.1 sec on, 0.1 sec off

count flashes

start when switch

is pressed:

0.5 sec on, 0.5 sec off

timeout:

60 sec

Press switch and count red and green flashes for

baud rate setting.

Release when wanted amount has been count.

Counts up to max. 5 and than starts at 0 again.

When counting failed, keep switch pressed and

restart counting for next attempt.

Note: selection of 0 means: No change

Instrument returns to normal running / operation mode. Changes are valid when they are made within the time-out times.

Value zero will be indicated by a period of 1 sec off (0.5 sec off + 0,5 sec off).

When value zero is wanted, press switch shortly and release it again within 1 sec.

Before each action of flash-counting, the LEDs to be used for counting will flash in a high frequency.

(Pattern: 0.1 sec on, 0.1 sec off). As soon as the switch is pressed-down, this LED (or both LEDs) will be off and the

counting sequence will start.

Changing node address, baud rate or parity in 'Configuration Mode' or in normal mode

The procedure for changing the baud rate, node address or parity for a FLOW-BUS or Modbus configuration over RS485 is

described in Section 3.5.3. In the list below the selectable bus parameters with corresponding values are presented.

When changing any of the parameters below in normal running/operation mode the communication with the

instrument may be lost. After a restart the instrument is available for communication on the newly selected

parameters. When in doubt activate the 'Configuration Mode' (38k4 and RS232 FLOW-BUS (Propar)) using the

micro-switch.

Fieldbus 2 selection

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

0…3

308

124/8

0xFC40/64577

This parameter sets the fieldbus type. Parameter value 0 = FLOW-BUS, 1 = Modbus RTU, 2 = Propar, 3 = Modbus ASCII