6 display filter, Display filter – Bronkhorst IQ+FLOW (till 01-07-2013) User Manual
Page 23
9.17.045
page 23
Controller Speed (Kspeed)
Type
Access
Range
FlowDDE
FlowBus
Modbus
Float
RW
0…3.4E+38 254
114/30
0xF2F0…0xF2F1/62193…62194
This parameter is the controller speed factor. PID-Kp is multiplied by this factor.
Ti (PID-Ti)
Type
Access
Range
FlowDDE
FlowBus
Modbus
Float
RW
0…1E+10 168
114/22
0xF2B0…0xF2B1/62129…62130
PID controller integration action in seconds. This value should not be changed.
Td (PID-Td)
Type
Access
Range
FlowDDE
FlowBus
Modbus
Float
RW
0…1E+10 169
114/23
0xF2B8…0xF2B9/62137…62138
PID controller differentiation action in seconds. The default value is 0.0. This value should not be changed.
Open from Zero control response (Kopen)
Type
Access
Range
FlowDDE
FlowBus
Modbus
Unsigned char
RW
0…255
165
114/18
0x0E52/3667
Controller response when starting-up from 0% (when valve opens). Value 128 is default and means: no correction.
Otherwise controller speed will be adjusted as follows:
−
=
⋅
(128
)
New response Old response
1.05
Kspeed
Normal Step response (Knormal)
Type
Access
Range
FlowDDE
FlowBus
Modbus
Unsigned char
RW
0…255
72
114/5
0x0E45/3654
Controller response during normal control (at setpoint step). Value 128 is default and means: no correction.
Otherwise controller speed will be adjusted as follows:
−
=
⋅
(128
)
New response Old response
1.05
Knormal
Stable Situation control response (Kstable)
Type
Access
Range
FlowDDE
FlowBus
Modbus
Unsigned char
RW
0…255
141
114/17
0x0E51/3666
Controller response when controller is stable (within band of 2% of setpoint). Value 128 is default and means: no
correction. Otherwise controller speed will be adjusted as follows:
−
=
⋅
(128
)
New response Old response
1.05
Kstable
4.1.6 Display filter
The output signal of an IQ
+
FLOW® instrument (measured value) is filtered. The filter has dynamic behaviour: when a
change in sensor signal is detected, the measured value will be less filtered than when the sensor signal is constant
and stable. There are two filter constants: Static Display Factor and Dynamic Display Factor. These two factors can be
transformed into time constants using the following formula:
factor
cycletime
factor
1
τ
−
=
⋅
The measured value is filtered with a first order low pass filter with a filter time constant between the two τ values.