beautypg.com

6 display filter, Display filter – Bronkhorst IQ+FLOW (till 01-07-2013) User Manual

Page 23

background image

9.17.045

page 23

Controller Speed (Kspeed)

Type

Access

Range

FlowDDE

FlowBus

Modbus

Float

RW 

0…3.4E+38 254

114/30

0xF2F0…0xF2F1/62193…62194

This parameter is the controller speed factor. PID-Kp is multiplied by this factor.

Ti (PID-Ti)

Type

Access

Range

FlowDDE

FlowBus

Modbus

Float

RW 

0…1E+10 168

114/22

0xF2B0…0xF2B1/62129…62130

PID controller integration action in seconds. This value should not be changed.

Td (PID-Td)

Type

Access

Range

FlowDDE

FlowBus

Modbus

Float

RW 

0…1E+10 169

114/23

0xF2B8…0xF2B9/62137…62138

PID controller differentiation action in seconds. The default value is 0.0. This value should not be changed.

Open from Zero control response (Kopen)

Type

Access

Range

FlowDDE

FlowBus

Modbus

Unsigned char

RW 

0…255

165

114/18

0x0E52/3667

Controller response when starting-up from 0% (when valve opens). Value 128 is default and means: no correction.

Otherwise controller speed will be adjusted as follows:

=

(128

)

New response Old response

1.05

Kspeed

Normal Step response (Knormal)

Type

Access

Range

FlowDDE

FlowBus

Modbus

Unsigned char

RW 

0…255

72

114/5

0x0E45/3654

Controller response during normal control (at setpoint step). Value 128 is default and means: no correction.

Otherwise controller speed will be adjusted as follows:

=

(128

)

New response Old response

1.05

Knormal

Stable Situation control response (Kstable)

Type

Access

Range

FlowDDE

FlowBus

Modbus

Unsigned char

RW 

0…255

141

114/17

0x0E51/3666

Controller response when controller is stable (within band of 2% of setpoint). Value 128 is default and means: no

correction. Otherwise controller speed will be adjusted as follows:

=

(128

)

New response Old response

1.05

Kstable

4.1.6 Display filter

The output signal of an IQ

+

FLOW® instrument (measured value) is filtered. The filter has dynamic behaviour: when a

change in sensor signal is detected, the measured value will be less filtered than when the sensor signal is constant

and stable. There are two filter constants: Static Display Factor and Dynamic Display Factor. These two factors can be

transformed into time constants using the following formula:

factor

cycletime

factor

1

τ

=

The measured value is filtered with a first order low pass filter with a filter time constant between the two τ values.