background image

9.17.045

page 20

4. Advanced operation

4.1 Reading and changing instrument parameters

4.1.1 Special parameters

!

All parameters described in this chapter have influence on the behaviour of the mass flow meter. Please

be aware that wrong settings can disorder the output. To avoid unintential changes, some parameters

are locked (shown by the symbol). To unlock parameters set parameter ‘Init Reset’ to ‘Unlocked’.

Init Reset

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

82/64

7

0/10

0x000A/11

The ‘Init Reset’ parameter is used to unlock advanced parameters for writing. This parameter can be set to the

following values:

Value

Mode

Instrument action

82

Locked

Advanced parameters are read-only

64

Unlocked

Advanced parameters are writeable and readable

This parameter is always set to ‘Locked’ at power-up.

Control Mode

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned int

RW

0…255

12

1/4

0x0024/37

The ‘Control mode’ is used to select different functions of the instrument. The following modes are available:

Value

Mode

Instrument action

Setpoint source

Master

source

Slave

factor

0

BUS/RS232

Controlling

RS232/RS485

1

Analog input

Controlling

Analog input

2

FLOW-BUS slave

Controlling as slave of other

instrument on bus

FLOW-BUS * slave

factor / 100%

FLOW-BUS

Slave

factor

3

Valve close

Close valve

4

Controller idle

Stand-by on BUS/RS232

Controlling is stopped; Valve Out

freezes in current position

5

Testing mode

Test mode enabled (factory only)

6

Tuning mode

Tuning mode enabled (factory only)

7

Setpoint 100%

Controlling at setpoint 100%

Fixed 100%

8

Valve fully open

Valve fully opened

9

Calibration mode Calibration mode enabled (factory

only)

10

Analog slave

Controlling as slave of other

instrument on analog input

Analog input *

slave factor / 100%

Analog input

Slave

factor

12

Setpoint 0%

Controlling at setpoint 0%

Fixed 0%

13

FLOW-BUS

analog slave

Controlling as slave of other

instrument on bus, slave factor is

set with signal on analog input

FLOW-BUS *

analog input *

slave factor / 100%

FLOW-BUS *

analog input

Analog

input

18

RS232

Controlling

RS232

20

Valve steering

Setpoint is redirected to Valve Out

with controller idle

21

Analog valve

steering

Analog input is redirected to Valve

Out with the controller idle

22

Valve safe state