2 identification, 3 fluid information, Identification – Bronkhorst IQ+FLOW (till 01-07-2013) User Manual

Page 21: Fluid information

background image

9.17.045

page 21

After power-up the control mode will be set to ‘Analog input’ or ‘BUS/RS232’, depending on the customer’s default

setting for analog or digital operation. Except when the actual control mode setting is other than 0, 1, 9 or 18 the

actual control mode setting is maintained. For more information see parameter ‘IOStatus’, section 4.2.2.

For dual interface operation or slave factors, see document nr. 9.17.023: Operational instructions for

digital instruments.

4.1.2 Identification

See also section 3.6.3.

Firmware Version

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char[5]

R

-

105

113/5

0xF128…0xF12A/61737…61739

Revision number of firmware, e.g ‘V1.11a’.

4.1.3 Fluid information

The following parameters give information about the selected fluid range

.

Fluid Number

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

0…7

24

1/16

0x0030/49

The ‘Fluid number’ is a pointer to the set of calbration parameters. Each selectable fluid has its own set of calibration

parameter values. Parameter value 0 = fluid 1 and parameter value 7 = fluid 8. Up to eight fluids can be stored in an

instrument. Default value = 0 (fluid 1).

Fluid Name

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char[10] RW 

-

25

1/17

0x8188…0x818C/33161…33165

This parameter consists of the name of the selected fluid number, e.g. ‘Air’.

Fluid Unit

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char[7]

RW 

-

129

1/31

0x81F8…0x81FB/33273…33276

The ‘Fluid Unit’ can be read by parameter ‘Capacity Unit’. This parameter contains the unit in maximal 7 characters.

Fluid Capacity (@100%)

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Float

RW 

±1E-10… ±1E+10

21

1/13

0x8168…0x8169/33129…33130

Capacity is the maximum value at 100% for direct reading in sensor readout units.

Fluid Capacity (@0%)

Type

Access

Range

FlowDDE

FLOW-BUS Modbus

Float

RW 

±1E-10… ±1E+10

183

33/22

0xA1B0…0xA1B1/41393…41394

This is the capacity zero point for direct reading in sensor readout units.

For using the ‘Capacity Unit Index’ or ‘Capacity Unit’ parameters, see document nr. 9.17.023: Operational

instructions for digital instruments.