beautypg.com

4 advanced measurement and control parameters, 5 controller parameters, Advanced measurement and control parameters – Bronkhorst IQ+FLOW (till 01-07-2013) User Manual

Page 22: Controller parameters

background image

9.17.045

page 22

4.1.4 Advanced measurement and control parameters

Measured Value (Fmeasure)

Type

Access

Range

FlowDDE FLOW-BUS Modbus

Float

R

-3.4E+38…3.4E+38

205

33/0

0xA100…0xA101/41217…41218

Floating point variable of the ‘Measured Value’. The ‘Fmeasure’ variable shows the measured value in the capacity and

capacity unit for which the instrument has been set. The ‘Fmeasure’ parameter is dependent of ‘Capacity’, ‘Capacity

Unit’, ‘Sensor Type’ and ‘Capacity 0%’.

Setpoint (Fsetpoint)

Type

Access

Range

FlowDDE FLOW-BUS Modbus

Float

RW

0…3.4E+38

206

33/1

0xA119…0xA11A/41241…41242

Floating point variable of the ‘Setpoint’. The ‘Fsetpoint’ variable shows the setpoint value in the capacity and capacity

unit for which the instrument has been set. The ‘Fsetpoint’ parameter is dependent of ‘Capacity’, ‘Capacity Unit’,

‘Sensor Type’ and ‘Capacity 0%’.

Valve Output

Type

Access

Range

FlowDDE

FLOW-BUS Modbus

Unsigned long

RW

0…16777215 55

114/1

0x001F/32

This parameter is the signal coming out of the controller, used for driving the valve. 0…16777215 corresponds with

approximately 0…60 mAdc.

4.1.5 Controller parameters

The controlling algorithm for the valve handled by the micro-controller consists of several parameters which can be

set. Although many parameters could be accessed, Bronkhorst® advises not to change these parameters because

during manufacturing the controller is optimized. Changing of controller settings should be performed by or under

supervision from trained service personnel only.

The picture below shows the basic controller diagram of the digital instrument. It consists of a standard PID controller

with a number of add-ons. Basically, when a faster or slower controller response is needed, only the controller speed

(Kspeed) or PID-Kp should be changed.

Kp (PID-Kp)

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Float

RW 

0…1E+10 167

114/21

0xF2A8…0xF2A9/62121…62122

PID controller proportional action, multiplication factor.