Page 8

Operational instructions for digital multibus instruments

9.17.023

Digital instruments can be operated by means of:

1. Analog interface. (0...5Vdc/0...10Vdc/0...20mA/4...20mA)

2. RS232 interface (connected to COM-port by means of special cable (Default speed 38400 Baud)

3. FLOW-BUS

4. PROFIBUS-DP

5. DeviceNet

6. Modbus

7. EtherCAT

Option 1 and 2 are always present on Multibus instruments. Option 3, 4, 5 and 6 are optional. Operation via analog

interface, RS232 interface and an optional field bus can be performed at the same time. A special parameter called

“control mode” indicates to which setpoint the controller should listen: analog or digital (via field bus or RS232). The

RS232 interface behaves like a FLOW-BUS interface. When using more digital interfaces at the same time, reading can

be done simultaneously without problems. When changing a parameter value, the last value send by an interface will

be valid.

Also the micro push-button switch and the LED’s on top of the instrument can be used for manual operation of some

options.

The green LED will indicate in what mode the instrument is active.

The red LED will indicate info / error / warning situations.