Mac-id – Bronkhorst Multibus User Manual
Page 45
![background image](https://www.manualsdir.com/files/776589/content/doc045.png)
BRONKHORST
®
Page 45
Operational instructions for digital multibus instruments
9.17.023
For MBC3 type of instruments the “configuration mode” is activated*
*MBC3 type instruments have additional functionality for Remote/manual install. It also sets the baud
rate and bus type for the main connector back to its default value as is 38K4 and type RS232.
This is called the “configuration mode”
11.3 M
ICRO
-S
WITCH USE FOR READING
/
SETTING ADDRESS
/
MAC-ID
AND BAUDRATE
11.3.1 General
The micro-switch can be used for several functions. The function it triggers may be depending on the present field
bus. Use the micro-switch always in combination with the LED’s to prevent errors. The following functions can be
triggered with the micro-switch.
•
Set instrument to default installation address/MAC-ID
•
Read bus-address/MAC-ID and baud rate
•
Change bus-address/MAC-ID and baud rate
•
Read control mode
•
Change control mode
To read or change settings by the micro-switch and LED’s, the number
can be separated in “tens” and “units”. The “tens” is the most left part
of the number. The “unit” is the most right decimal of the number.
The easiest way to set an address / baud rate is by using the rotary switches on the instrument (if
present). Remember that the rotary switch setting overrides software setting at start-up if the switches
are not in the soft-address position.
1
6
Tens
Green LED
Use of “tens” and “unit”
Address
Unit
Red LED