Bronkhorst Multibus User Manual

Page 46

background image

BRONKHORST

®

Page 46

Operational instructions for digital multibus instruments

9.17.023

11.3.2 Readout bus-address/MAC-ID and baudrate:

Pressing the switch 3x briefly with intervals of max. 1 second in normal running/operation mode will trigger the

instrument to “show” its bus address/MAC-ID and baud rate. For indication the bus-address/MAC-ID the green LED

will flash the amount of tens and the red LED the amount of units in the number. For indication of baud rate setting,

both LED’s will flash. The flashes are called “count-flashes” and have a pattern of 0.5 sec. on, 0.5 sec. off.

LED indications for bus-address/MAC-ID and baud rate (press switch 3x briefly)

LED

LED

Time

Indication

Green

Red

amount of count flashes

(0...12)

Off

0 ... 12 sec.

Maximum

tens in bus-address/MAC-ID for instrument

off

Amount of count flashes

(0...9)

0 ... 9 sec.

Maximum

units in bus-address/MAC-ID for instrument

amount of count flashes

(0...10)

amount of count flashes

(0...10)

0 ... 10 sec.

Maximum

baud rate setting for instrument

Value zero will be indicated by a period of 1 sec. off (0.5 sec. off + 0.5 sec. off).

Examples:

• For bus address/MAC-ID 35 the green LED will flash 3 times and the red LED will flash 5 times.

• For bus address/MAC-ID 20 the green LED will flash 2 times and the red LED will flash 0 times.

• For bus address/MAC-ID 3 the green LED will flash 0 times and the red LED will flash 3 times.

• For bus address 126 the green LED will flash 12 times and the red LED will flash 6 times.

Baud rate index table for indication on the LED’s (in baud)

FLOW-BUS

PROFIBUS-DP

DeviceNet

Modbus

EtherCAT

1

2

187500

400000*

0

1

2

3

4

5

6

7

8

9

10

not detected

9600

19200

45450

93750

187500

500000

1500000

3000000

6000000

12000000

1

2

3

125000

250000

500000

1

2

3

4

5

9600

19200

38400

57600*

115200*

1

100000000

*MBC3 type instruments have additional baud rates available for the several field busses.

EtherCAT bus address is always ‘0’.

Examples:

• For PROFIBUS-DP baud rate readout of 12000000 Baud, both LED’s will flash 10 times.

• For DeviceNet baud rate readout of 250000 Baud, both LED’s will flash 2 times.