5 Installation
BECKHOFF
Drive Technology
38
Version : 4.6
AX5000
5.2.3.2
Connection example - wiring in series without AX Bridge
Wire the relevant connections using individual cables.
CAUTION
Hazard to inviduals and equipment
•
Please ensure that the final supply network connection cable is
adequately dimensioned. The dimensioning depends on the total rated
current and must comply with EN60204-1.
•
To establish a DC link system wire the X02 connections with a suitable
cable. Voltages up to 890 V may be present.
•
The connectors are designed for a maximum current of 41 A and a
maximum conductor cross-section of 6 mm².
•
Avoid phase reversal between the devices!
The supply connection is established as described in sections 5.2.1 and 5.2.2.
- Bus Terminal System (19 pages)
- EP-xxxx-xxxx (19 pages)
- BK2000 (30 pages)
- LC3100 (67 pages)
- BK4000 (28 pages)
- BK3xx0 (95 pages)
- BK5000 (12 pages)
- LC5200 (32 pages)
- BK7000 (29 pages)
- BK7500 (32 pages)
- BK7300 (40 pages)
- BK8100 (26 pages)
- BC2000 (28 pages)
- BC3100 (51 pages)
- BC7300 (48 pages)
- BC8100 (36 pages)
- BC3150 (112 pages)
- KL1012 (2 pages)
- KL1114 (2 pages)
- KL1164 (1 page)
- KL1232-xxxx (4 pages)
- KL1501 (19 pages)
- KL1512 (15 pages)
- KL2521-0024 (18 pages)
- KL2512 (21 pages)
- KL2612 (4 pages)
- KL2622 (9 pages)
- KL3062 (24 pages)
- KL3064 (20 pages)
- KL4132 (19 pages)
- KL4034 (25 pages)
- KL3302 (23 pages)
- KL3351 (18 pages)
- KS3681 (43 pages)
- KL4112 (18 pages)
- KL5001 (16 pages)
- KL5051 (17 pages)
- KL5101-0012 (21 pages)
- KS5111-0000 (21 pages)
- KL5121 (19 pages)
- KL6021 (20 pages)
- KL6051 (17 pages)
- Z1000 (2 pages)
- KL6071 (12 pages)
- Z1003 (2 pages)