10 x13 - motor connection (power - only ax5140) – BECKHOFF AX5000 1,5 A - 40 A User Manual
Page 26

4 Product description
BECKHOFF
Drive Technology
26
Version : 4.6
AX5000
4.7.9
X13 (channel A) , X23 (channel B) - motor connection (power)
(AX5101 - AX5125 und AX520x)
Terminal point
Connection
U
Motor connection U
V+
Motor connection V
W
Motor connection W
PE
Protective conductor
Shroud
Screen
4.7.10 X13 - motor connection (power - only AX5140)
Terminal point
Connection
U
Motor connection U
V+
Motor connection V
W
Motor connection W
PE
Protective conductor
Shroud
Screen
Attention
Grounding shield!
The grounding shield of the motor is connected via the shield plate in the
motor connector. Please tighten the knurled screws of the motor connector
with a screwdriver. It is possible that some feedback problems may caused
due to a poor shield connection of the motor.
4.7.11 X14 (channel A), X24 (channel B)-motor brake, thermal contact, OCT
AX5000-xxxx-0000 (Hardware 1)
Terminal point
Connection
Output current
T-
Temp. -
*
T+
Temp. +
*
PE
Signal pair screen
B-
Brake GND
B+
Brake (U
p
) +
1.5 A max.
*) Switch, KTY 83-1xx or KTY 84-1xx