1 mains supply connection (x01), 2 internal protection, ce-compliant – BECKHOFF AX5000 1,5 A - 40 A User Manual
Page 33

BECKHOFF
Drive Technology
5 Installation
AX5000
Version : 4.6
33
5.2.1
Mains supply connection (X01)
The servo drives of the AX5000 series are equipped with a wide voltage input "
X01" and can
be connected to voltage systems between single-phase 100 V
AC -10%
- 240 V
AC +10%
and
three-phase 100 V
AC -10%
- 480 V
AC +10%
.
Note
Connection to the standard mains supply (TT/TN) with earthed centre is
described below. Details for connections to other supply systems (e.g. IT-
mains supply, isolating transformer etc.) can be found in the “AX5000 User
manual” on the enclosed CD or can be downloaded from our website at
single-phase 100
-10%
- 240
+10%
V
AC
three-phase 100
-10%
- 480
+10%
V
AC
5.2.1.1
External protection for individual devices, CE-compliant
CAUTION
Fire hazard through short circuit!
•
The following data refer to individual devices. Please note the total
current of all connected devices in a multi-axis system.
•
The recommended fuses are designed for line protection. The servo
drives feature integrated self-protection.
Single-phase
Fusing
AX5101 AX5103 AX5106 AX5201 AX5203 AX5206
AC supply
*)
10 A
10 A
16 A
10 A
16 A
20 A
24 V supply
*)
5 A
Brake resistor
electronic
*) Application class "gG" mains fuses according to IEC 60269 with characteristic “T” or
"C" type automatic circuit breakers must be used.
Three-phase
Fusing
AX
5101 5103 5106 5112 5118 5125 5140 5201 5203 5206
AC supply
*)
6 AT 6 A 10 A 20 A 35 A 35 A 50 A 10 A 10 A 20 A
24 V supply
*)
5 A
Brake resistor
elektronisch
*) Application class "gG" mains fuses according to IEC 60269 with characteristic “T” or
"C" type automatic circuit breakers must be used.
5.2.1.2
Internal protection, CE-compliant
Circuit
Fuse
24 V - system voltage
3.4 AF
24 V - peripheral voltage
electronic
Brake resistor
electronic