Overexcitation limiter, Underexcitation limiter, Soft start function (avr mode only) – Basler Electric DECS-100 User Manual
Page 17: Voltage matching, Metering (bestcoms™), Overexcitation limiter -5, Underexcitation limiter -5, Soft start function (avr mode only) -5, Voltage matching -5, Metering (bestcoms™) -5
9287500991 Rev M
DECS-100 General Information
1-5
Overexcitation Limiter
Pickup
Range:
0 to 15 Adc
Increment:
0.001 Adc
Alarm Time Delay
Range:
0 to 10 s
Increment:
1 s
Underexcitation Limiter
Pickup
Range:
0 to 100% of rated vars
Increment:
1%
Alarm Time Delay
Range:
0 to 10 s
Increment:
1 s
Soft Start Function (AVR Mode Only)
Time Adjust Range:
1 to 7,200 s
Increment:
1 s
Voltage Matching
Accuracy:
Generator rms voltage is matched with the bus rms voltage to within
±0.5% of the generator voltage.
Time Adjustment
Range:
1 to 300 s
Increment:
0.01 s
Metering (BESTCOMS™)
Generator Voltage
Range:
10 V to 79 kV
Accuracy:
±0.5% (at 25
°C)
Generator Current
Range:
0.04 to 3,000 Aac for 1 A CT (Not to exceed nominal CT rating)
0.2 to 15,000 Aac for5 A CT (Not to exceed nominal CT rating)
Accuracy:
±0.5% (at 25
°C)
Frequency
Range:
40 to 65 Hz
Accuracy:
±0.2 Hz (at 25
°C)
Field Voltage
Range:
0 to 200 Vdc
Accuracy:
±5.0% (at 25
°C)
Field Current
Range:
0 to 20 A
Accuracy:
±0.5% (at 25
°C)
Bus Voltage
Range:
10 V to 79 kV
Accuracy:
±0.5% (at 25
°C)
Auxiliary DC Input
Range:
–3 V to +3 V
Accuracy:
±0.5% (at 25
°C)