Fcr (manual) operating mode, Var operating mode (optional), Pf operating mode (optional) – Basler Electric DECS-100 User Manual
Page 16: Parallel compensation, Field overvoltage protection, Generator overvoltage protection, Fcr (manual) operating mode -4, Var operating mode (optional) -4, Pf operating mode (optional) -4, Parallel compensation -4

1-4
DECS-100 General Information
9287500991 Rev M
Figure 1-2. Typical V/Hz Curves
FCR (Manual) Operating Mode
Adjustment Range:
0 to 7 Adc
Increment:
0.01 Adc
Var Operating Mode (Optional)
Adjustment Range:
–100 to 100%
Increment:
0.1%
PF Operating Mode (Optional)
Adjustment Range:
0.6 lag to 0.6 lead
Increment:
0.001
Parallel Compensation
Modes:
Reactive Droop and Reactive Differential (cross-current)
∗
Droop Adjust Range:
0 to 10%
Increment:
1%
∗ Burden can exceed 1 VA if external resistors are added to the CT circuit.
Field Overvoltage Protection
Pickup Range:
0 to 250 Vdc
Time Delay:
10 s (fixed)
Generator Overvoltage Protection
Pickup
Range:
100 to 120% of system voltage setting
Increment:
1.0%
Alarm Time Delay
Range:
0 to 10 s
Increment:
1 s